445
7: Drive S7 Passthrough
Setting Value
Function
Description
7
Drive S7 Passthrough
Drive Multi-function input S7.
21: Run (AUTO)
Setting Value
Function
Description
21
Run (AUTO)
Starts and stops the bypass.
22: Run Enable - Safety (NC)
Setting Value
Function
Description
22
Run Enable - Safety (NC)
Stops the bypass.
Stops the bypass from running. Parameter
Z2-31
controls the message shown on the HOA keypad when this input is
open.
It is possible to program more than one digital input terminal to
Z1-0x = 22 [Run Enable - Safety (NC)]
.
23: Run Interlock (BAS)
Setting Value
Function
Description
23
Run Interlock (BAS)
Stops the drive and triggers alarm
AL02
Use
Z1-13
and
Z1-15
to modify Interlock settings.
24: Remote Transfer to Bypass
Setting Value
Function
Description
24
Remote Transfer to Bypass
Stops the drive and turns on the bypass when a Run command is issued while in Drive Mode.
Parameter
Z1-05
controls the fault for this mode. Parameter
Z1-40
controls the length of time that the drive must be
faulted before it switches to Bypass Mode.
25: Emergency Override Bypass
Setting Value
Function
Description
25
Emergency Override Bypass
Stops the drive and turns on the bypass when a Run command is issued while in Drive Mode.
The bypass runs continuously. Faults and alarms to not have an effect.
26: Emergency Override Drive (FWD)
Setting Value
Function
Description
26
Emergency Override Drive
(FWD)
The bypass controller stays in this state even if the drive faults or is unavailable.
The preset speed is equal to
Z1-10
.
27: Motor OR Select
Setting Value
Function
Description
27
Motor OR Select
2-Motor OR function; 0/1 for Motor 1/2.
Parameter
Z1-11
defines the behavior.
28: Motor AND Select
Setting Value
Function
Description
28
Motor AND Select
2-Motor AND function; 0/1 for 1/2 motor.
If 1 motor, then look to Motor OR input for selected motor. Parameter
Z1-11
defines the behavior.
29: External Overload Motor 1 (NC)
Setting Value
Function
Description
29
External Overload Motor 1
(NC)
When input is open, it will trigger an
oL
fault and open bypass (K3) contactors.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...