YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
651
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
S3-06
(321F)
RUN
PI2 Control Proportional
Gain
Sets the proportional gain of the PI2 Control. Set this parameter to 0.00 to disable
proportional control.
1.00
(0.00 - 25.00)
S3-07
(3220)
RUN
PI2 Control Integral Time Sets the integral time for the suction pressure control. Set this parameter to 0.00 to disable
the integrator.
1.0 s
(0.0 - 360.0 s)
S3-08
(3221)
RUN
PI2 Control Integral Max
Limit
Sets the maximum output possible from the integrator.
100.0%
(0.0 - 100.0%)
S3-09
(3222)
RUN
PI2 Control Output Upper
Limit
Sets the maximum output possible from the PI Auxiliary Control function.
100.0%
(0.0 - 100.0%)
S3-10
(3223)
RUN
PI2 Control Output
Lower Limit
Sets the minimum output possible from the PI Auxiliary Control function.
0.0%
(-100.0 - +100.0%)
S3-11
(3224)
PI2 Control Output Level
Sel
Sets the PI2 controller output direction.
0 : Direct Acting (Normal Output)
1 : Inverse Acting (Reverse Output)
0
(0, 1)
S3-12
(3225)
RUN
PI2 Control Disable
Mode Sel
Sets what
U5-20 [PI2 Control Output]
will output when disabled.
0 : No Output (0%)
1 : Lower Limit (S3-10)
2 : Setpoint
0
(0 - 2)
S3-13
(3226)
RUN
PI2 Control Low
Feedback Lvl
Sets the secondary PI low feedback detection level.
Note:
Parameters
S3-04 [PI2 Control Unit Selection]
,
S3-03 [PI2 Control Decimal Place
Pos]
, and
S3-02 [PI2 Control Transducer Scale]
set the unit, resolution, and upper
limit.
0.00
(0.00 - 600.00)
S3-14
(3227)
RUN
PI2 Control Low
Feedback Time
Sets the secondary PI low feedback detection delay time in seconds.
1.0 s
(0.0 - 25.5 s)
S3-15
(3228)
RUN
PI2 Control High
Feedback Lvl
Sets the secondary PI high feedback detection level.
Note:
Parameters
S3-04 [PI2 Control Unit Selection]
,
S3-03 [PI2 Control Decimal Place
Pos]
, and
S3-02 [PI2 Control Transducer Scale]
set the unit, resolution, and upper
limit.
100.00
(0.00 - 600.00)
S3-16
(3229)
RUN
PI2 Control High
Feedback Time
Sets the secondary PI high feedback detection delay time in seconds.
1.0 s
(0.0 - 25.5 s)
S3-17
(322A)
RUN
PI2 Control Feedback Det
Sel
Sets when the low and high feedback detection multifunction outputs (71h and 72h) for
PI2 Control are active.
0 : While PI2 Control Enabled
1 : Always
Note:
Feedback level detection compares PI2 Control Feedback from analog input
H3-xx =
26 [MFAI Function Selection = PI2 Control Feedback]
to these parameters:
•
S3-13 [PI2 Control Low Feedback Lvl]
for low feedback level detection
•
S3-15 [PI2 Control High Feedback Lvl]
for high feedback level detection
0
(0, 1)
S3-18
(322B)
RUN
PI2 Control Custom Unit
1
Sets the first character of the PI2 Control custom unit display when
S3-04 = 49 [PI2
Control Unit Selection = Custom(S3-18~20)]
.
41
(20 - 7A)
S3-19
(322C)
RUN
PI2 Control Custom Unit
2
Sets the second character of the PI2 Control custom unit display when
S3-04 = 49 [PI2
Control Unit Selection = Custom(S3-18~20)]
.
41
(20 - 7A)
S3-20
(322D)
RUN
PI2 Control Custom Unit
3
Sets the third character of the PI2 Control custom unit display when
S3-04 = 49 [PI2
Control Unit Selection = Custom(S3-18~20)]
.
41
(20 - 7A)
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...