296
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
■
H3-04: Terminal A1 Bias Setting
No.
(Hex.)
Name
Description
Default
(Range)
H3-04
(0412)
RUN
Terminal A1 Bias Setting
Sets the bias of the analog signal input to MFAI terminal A1.
0.0%
(-999.9 - +999.9%)
This parameter sets the bias for the function set for terminal A1 as a percentage when 0 V (4 mA or 0 mA) is input.
Use this parameter and
H3-03 [Terminal A1 Gain Setting]
to adjust the characteristics of the analog input signal to
terminal A1.
■
H3-09: Terminal A2 Signal Level Select
No.
(Hex.)
Name
Description
Default
(Range)
H3-09
(0417)
Terminal A2 Signal Level
Select
Sets the input signal level for MFAI terminal A2.
2
(0 - 3)
0 : 0-10V (LowLim=0)
The voltage signal is 0 Vdc to 10 Vdc. The minimum input level is limited to 0%, so that a negative input signal due
to gain and bias settings will be read as 0%.
2 : 4 to 20 mA
The current signal is 4 mA to 20 mA. The minimum input level is limited to 0%, so that a negative input signal due to
gain and bias settings will be read as 0%.
3 : 0 to 20 mA
The current signal is 0 mA to 20 mA. The minimum input level is limited to 0%, so that a negative input signal due to
gain and bias settings will be read as 0%.
Note:
When
H3-09 = 0
, set Jumper switch S1 to the V side (voltage). When
H3-09 = 2, 3
, set Jumper switch S1 to the I side (current). The default
setting is the I side (current).
■
H3-10: Terminal A2 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
H3-10
(0418)
Terminal A2 Function
Selection
Sets the function for MFAI terminal A2.
Determined by b5-01
(0 - 31)
Note:
The default setting for
H3-10
changes when
b5-01 [PID Mode Setting]
changes:
•
b5-01 = 0 [Disabled]
: 0
•
b5-01 ≠ 0
: B
■
H3-11: Terminal A2 Gain Setting
No.
(Hex.)
Name
Description
Default
(Range)
H3-11
(0419)
RUN
Terminal A2 Gain Setting
Sets the gain of the analog signal input to MFAI terminal A2.
100.0%
(-999.9 - +999.9%)
When 10 V (or 20 mA) is input, this parameter sets the reference quantity for the function set for terminal A2 as a
percentage.
Use this parameter and
H3-12 [Terminal A2 Bias Setting]
to adjust the characteristics of the analog input signal to
terminal A2.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...