266
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
■
A: Accel/Decel Ramp Hold
Setting Value
Function
Description
A
Accel/Decel Ramp Hold
Momentarily pauses motor acceleration and deceleration when the terminal is turned ON, retains the output frequency that was
stored in the drive at the time of the pause, and restarts motor operation.
If the terminal is deactivated, the drive restarts acceleration and deceleration.
When the acceleration/deceleration ramp hold terminal is activated and
d4-01 = 1 [Freq Reference Retention Select =
Enabled]
, the drive will store the output frequency in memory. While the acceleration/deceleration ramp hold
command is activated, the drive will always restart the motor at this output frequency.
Note:
Refer to
d4-01: Freq Reference Hold Selection on page 240
for more information.
■
B: Overheat Alarm (oH2)
Setting Value
Function
Description
B
Overheat Alarm (oH2)
Sets the drive to display an
oH2 [Drive Overheat Warning]
alarm when the input terminal is ON. The alarm does not have an effect
on drive operation.
■
C: Analog Terminal Enable Selection
Setting Value
Function
Description
C
Analog Terminal Enable
Selection
Sets the command that enables or disables the terminals selected in
H3-14 [Analog Input Terminal Enable Sel]
.
ON : Terminal selected with
H3-14
is enabled
OFF : Terminal selected with
H3-14
is disabled
■
F: Not Used
Setting Value
Function
Description
F
Not Used
Use this setting for unused terminals or to use terminals in through mode.
Through Mode uses the signal input to the terminal as a digital input for the upper sequence through a communication
option or MEMOBUS/Modbus communications. This input signal does not have an effect on drive operation.
■
14: Fault Reset
Setting Value
Function
Description
14
Fault Reset
Sets the command to reset the current fault when the Run command is inactive.
If the drive detects a fault, the drive will activate the fault relay output, turn off the output, and the motor will coast to
stop.
If the drive detects a fault for which you can set the stopping method, apply the appropriate Stopping Method. Then
push
(RESET) on the keypad to turn the Run command OFF, or activate the fault reset terminal to reset the fault.
Note:
The drive ignores the fault reset command when the Run command is active. Remove the Run command before trying to reset a fault.
■
15: Fast Stop (N.O.)
Setting Value
Function
Description
15
Fast Stop (N.O.)
Sets the command to ramp to stop in the deceleration time set in
C1-09 [Fast Stop Time]
when the input terminal is activated while
the drive is operating.
If you cancel the fast stop input, the drive will not restart the motor until you meet these conditions:
•
Fully stop the motor
•
Cancel the Run command
•
Cancel the fast stop command
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...