272
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
■
6A: Drive Enable
Setting Value
Function
Description
6A
Drive Enable
Sets the function to show
dnE [Drive Enabled]
on the keypad and ignore Run commands when the terminal is OFF.
If you input the Run command before you turn ON the Drive Enable terminal, you must input the Run command
again to operate the drive. When you deactivate the terminal set for Drive Enable while the drive is operating, the
drive will use the stopping method set in
b1-03 [Stopping Method Selection]
to stop the motor.
ON : Run command is accepted.
OFF : Run command is disabled. When the drive is running, it stops according to
b1-03
setting.
■
70: Drive Enable 2
Setting Value
Function
Description
70
Drive Enable 2
Sets the function to show
dnE [Drive Enabled]
on the keypad and ignore Run commands when the terminal is OFF.
When you input the Run command before you turn ON the Drive Enable 2 terminal, it is not necessary to remove and
apply the Run command again. The drive will start to operate when the Run command and Drive Enable 2 are both
ON. If you turn OFF the terminal set for Drive Enable while the drive is operating, the drive will use the stopping
method set in
b1-03 [Stopping Method Selection]
to stop the motor.
ON : Run command is accepted.
OFF : Run command is disabled. When the drive is running, it stops according to
b1-03
setting.
■
82: PI Switch to Aux
Setting Value
Function
Description
82
PI Switch to Aux
Sets
YF-xx [PI Auxiliary Control]
parameters as primary PI loop parameters and disables
b5-xx [PID Control]
.
Note:
When this input is active,
YF-xx [PI Auxiliary Control]
parameters will always be the primary PI loop parameters. Parameter
YF-20 [PI Aux
Main PI Speed Control]
does not have an effect.
■
83: Dedicated Multi-Setpoint YA-02
Setting Value
Function
Description
83
Dedicated Multi-Setpoint
YA-02
Sets the function to set the PID setpoint to
YA-02 [Setpoint 2]
.
Note:
If you use this function and one of
H1-xx = 3E or 3F [PID Setpoint Selection 1 or 2]
at the same time, the drive will detect an
oPE03 [Multi-
Function Input Setting Err]
.
ON :
YA-02
is PID setpoint.
OFF :
YA-01 [Setpoint 1]
,
YA-03 [Setpoint 3]
, or
YA-04 [Setpoint 4]
is PID setpoint.
■
84: Dedicated Multi-Setpoint YA-03
Setting Value
Function
Description
84
Dedicated Multi-Setpoint
YA-03
Sets the function to set the PID setpoint to
YA-03 [Setpoint 3]
. Set this function and
H1-xx = 83 [Dedicated Multi-Setpoint YA-02]
at
the same time.
Note:
If you use this function and one of
H1-xx = 3E or 3F [PID Setpoint Selection 1 or 2]
at the same time, the drive will detect an
oPE03 [Multi-
Function Input Setting Err]
.
ON :
YA-03
is PID setpoint.
OFF :
YA-01 [Setpoint 1]
,
YA-02 [Setpoint 2]
, or
YA-04 [Setpoint 4]
is PID setpoint.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...