3.3
Main Circuit Wiring
This section gives information about the functions, specifications, and procedures necessary to safely and correctly
wire the main circuit in the bypass.
NOTICE:
Damage to Equipment. Do not energize and de-energize the bypass more frequently than one time each 30 minutes. If
you frequently energize and de-energize the bypass, it can cause failure.
Note:
Soldered wire connections can become loose over time and cause unsatisfactory performance.
◆
Narrow Bypass Input and Output Power Wiring Connections
The input disconnect switch is located in the upper right hand side of the bypass. The three-phase input power
connection is made to the input terminals of the disconnect. Refer to
for a representative example. Motor
Terminal Block TB1 is mounted to the contactor assembly or back panel (depending on rating), just above the bypass
contactor. The bypass three-phase output power connection to the motor is made to Terminal Block TB1.
Note:
The location of components are different for different bypass models.
A - Drive output contactor K2
B - Input contactor K1
C - Motor connections
D - Input power terminals
E - Ground screw
F - A2 bypass control board
G - 120 V control transformer
H - Bypass contactor K3
Figure 3.3 Narrow Bypass Circuit Components Example
E
F
C
B
A
H
G
D
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...