b3-25: Speed Search Wait Time
No.
(Hex.)
Name
Description
Default
(Range)
b3-25
(01C8)
Expert
Speed Search Wait Time
Sets the length of time the drive will wait to start the Speed Search Retry function.
0.5 s
(0.0 - 30.0 s)
If the drive detects these faults during speed search, increase the setting value:
•
oC [Overcurrent]
•
ov [Overvoltage]
•
SEr [Speed Search Retries Exceeded]
■
b3-26: Direction Determination Level
No.
(Hex.)
Name
Description
Default
(Range)
b3-26
(01C7)
Expert
Direction Determination
Level
Sets the level to find the motor rotation direction. Increase the value if the drive cannot find the
direction.
1000
(40 to 60000)
■
b3-27: Speed Search RUN/BB Priority
No.
(Hex.)
Name
Description
Default
(Range)
b3-27
(01C9)
Expert
Speed Search RUN/BB
Priority
Sets the conditions necessary to start Speed Search.
0
(0, 1)
Executes
Speed Search from Fmax or Fref [H1-xx = 61/62]
for initial speed searches or from the MFDI terminal.
0 : SS Only if RUN Applied Before BB
1 : SS Regardless of RUN/BB Sequence
■
b3-31: Spd Search Current Reference Lvl
No.
(Hex.)
Name
Description
Default
(Range)
b3-31
(0BC0)
Expert
Spd Search Current
Reference Lvl
Sets the current level that decreases the output current during Current Detection Speed Search.
1.50
(1.50 - 3.50)
Set this parameter as a ratio of
E2-03 [Motor No-Load Current]
. The setting is a ratio with respect to 30% of the
motor rated current when
E2-03
≤
E2-01 [Motor Rated Current]
× 0.3.
■
b3-32: Spd Search Current Complete Lvl
No.
(Hex.)
Name
Description
Default
(Range)
b3-32
(0BC1)
Expert
Spd Search Current
Complete Lvl
Sets the current level that completes Speed Search.
1.20
(0.00 - 1.49)
The Current Detection Speed Search gradually decreases the output frequency to search for the motor speed when the
output current is equal to or less than Speed Search Current Complete Level.
Set this parameter as a ratio of
E2-03 [Motor No-Load Current]
. The setting is a ratio with respect to 30% of the
motor rated current when
E2-03
≤
E2-01 [Motor Rated Current]
× 0.3.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...