YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
295
Note:
•
Refer to H3-xx
“
MFAI Setting Values
”
for the analog input setting values.
•
When you will not use the terminal, set
H3-40 to H3-42 = F
. The through mode function is not supported.
•
You cannot use
H3-40 to H3-42
to set these MFAI terminals:
H3-xx Setting Value
Function
0
Frequency Reference
1
Frequency Gain
2
Auxiliary Frequency Reference 1
3
Auxiliary Frequency Reference 2
◆
H3: MFAI Parameters
■
H3-01: Terminal A1 Signal Level Select
No.
(Hex.)
Name
Description
Default
(Range)
H3-01
(0410)
Terminal A1 Signal Level
Select
Sets the input signal level for MFAI terminal A1.
0
(0 - 3)
0 : 0 to 10V (Lower Limit at 0)
The voltage signal is 0 Vdc to 10 Vdc. The minimum input level limit is 0%. The drive will read a negative input
signal caused by gain and bias settings as 0%.
2 : 4 to 20 mA
The current signal is 4 mA to 20 mA. The minimum input level limit is 0%. The drive will read a negative input
signal caused by gain and bias settings as 0%.
3 : 0 to 20 mA
The current signal is 0 mA to 20 mA. The minimum input level limit is 0%. The drive will read a negative input
signal caused by gain and bias settings as 0%.
Note:
When
H3-01 = 0
, set Jumper switch S1 to the V side (voltage). When
H3-01 = 2, 3
, set Jumper switch S1 to the I side (current). The default
setting is the V side (voltage).
■
H3-02: Terminal A1 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
H3-02
(0434)
Terminal A1 Function
Selection
Sets the function for MFAI terminal A1.
0
(0 - 31)
■
H3-03: Terminal A1 Gain Setting
No.
(Hex.)
Name
Description
Default
(Range)
H3-03
(0411)
RUN
Terminal A1 Gain Setting
Sets the gain of the analog signal input to MFAI terminal A1.
100.0%
(-999.9 - +999.9%)
This parameter sets the quantity of reference for the function set for terminal A1 as a percentage when 10 V (or 20
mA) is input.
Use this parameter and
H3-04 [Terminal A1 Bias Setting]
to adjust the characteristics of the analog input signal to
terminal A1.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...