YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
701
■
Executable Functions
A controller can do these operations with serial communications. Parameter settings (except
H5-xx
) do not have an
effect on the availability of these operations.
•
Monitor the bypass status and operate the bypass
•
Set and view parameters
•
Fault Reset Procedure
■
Bypass Control
To use external commands to set the frequency references and motor run/stop with serial communications, set these
parameters as specified by the application:
•
b1-01 = 2 [Frequency Reference Selection 1 = Serial Communications]
•
b1-02 = 2 or 8 [Run Command Selection 1 = Serial Communications or AUTO C Serial Run]
For more information about operation mode selection, refer to
b1-01
and
b1-02
.
◆
BACnet Objects Supported
■
Present Value Access
The Present Value (PV) of BACnet objects can always be read. Some PVs can also be written or commanded. A
commandable PV is almost the same as the writable PV, but the value is actually written into a priority array. The
value that has the highest priority in the array will be used by the drive.
Table 10.3 Present Value Access Types and Descriptions
PV Access
Name
Description
C
Commandable
Value written to a priority array. The highest priority value in the array is then written to the drive.
R
Readable
Value is read-only
W
Writable
Value written to the drive
■
Supported Properties of Objects
Table 10.4 Object Properties
Property
Object Type
Device
Analog
Input
(AI)
Analog
Output
(AO)
Analog
Value
(AV)
Binary
Input
(BI)
Binary
Output
(BO)
Binary
Value
(BV)
Object_Identifier
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Object_Name
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Location
Yes
-
-
-
-
-
-
Object_Type
Yes
Yes
Yes
Yes
Yes
Yes
Yes
System_Status
Yes
-
-
-
-
-
-
Vendor_Name
Yes
-
-
-
-
-
-
Vendor_Identifier
Yes
-
-
-
-
-
-
Model_Name
Yes
-
-
-
-
-
-
Firmware_Revision
Yes
-
-
-
-
-
-
Protocol_Version
Yes
-
-
-
-
-
-
Protocol_Revision
Yes
-
-
-
-
-
-
Protocol_Services_Supported
Yes
-
-
-
-
-
-
Protocol_Object_Types_Supported
Yes
-
-
-
-
-
-
Object_List
Yes
-
-
-
-
-
-
Max_ADPU_Length_Accepted
Yes
-
-
-
-
-
-
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...