236
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Note:
•
The upper limit value changes when the
E1-04 [Maximum Output Frequency]
and
d2-01 [Frequency Reference Upper Limit]
values
change. Calculate the upper limit value with this formula:
Upper limit value = (
E1-04
) × (
d2-01
) / 100
•
To set
d1-01
to 1-step speed parameter in a multi-step speed operation, set
b1-01 = 0 [Frequency Reference Selection 1 = Keypad]
.
■
d1-02: Reference 2
No.
(Hex.)
Name
Description
Default
(Range)
d1-02
(0281)
RUN
Reference 2
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
.
0.00 Hz
(0.00 - 400.00 Hz)
Note:
•
The upper limit value changes when the
E1-04 [Maximum Output Frequency]
and
d2-01 [Frequency Reference Upper Limit]
values
change.
•
To set
d1-02
to Multi-Step Speed 2, set
H3-02 and H3-10 ≠ 2 [MFAI Function Select ≠ Auxiliary Frequency Reference 1]
.
■
d1-03: Reference 3
No.
(Hex.)
Name
Description
Default
(Range)
d1-03
(0282)
RUN
Reference 3
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
.
0.00 Hz
(0.00 - 400.00 Hz)
Note:
•
The upper limit value changes when the
E1-04 [Maximum Output Frequency]
and
d2-01 [Frequency Reference Upper Limit]
values
change.
•
To set
d1-03
to Multi-Step Speed 3, set
H3-02 and H3-10 ≠ 3 [MFAI Function Select ≠ Auxiliary Frequency Reference 2]
.
■
d1-04: Reference 4
No.
(Hex.)
Name
Description
Default
(Range)
d1-04
(0283)
RUN
Reference 4
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
.
0.00 Hz
(0.00 - 400.00 Hz)
Note:
•
The upper limit value changes when the
E1-04 [Maximum Output Frequency]
and
d2-01 [Frequency Reference Upper Limit]
values
change.
•
This parameter sets the frequency reference of Multi-Step Speed 4.
■
d1-05: Reference 5
No.
(Hex.)
Name
Description
Default
(Range)
d1-05
(0284)
RUN
Reference 5
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
.
0.00 Hz
(0.00 - 400.00 Hz)
Note:
•
The upper limit value changes when the
E1-04 [Maximum Output Frequency]
and
d2-01 [Frequency Reference Upper Limit]
values
change.
•
This parameter sets the frequency reference of Multi-Step Speed 5.
■
d1-06: Reference 6
No.
(Hex.)
Name
Description
Default
(Range)
d1-06
(0285)
RUN
Reference 6
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
.
0.00 Hz
(0.00 - 400.00 Hz)
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...