390
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Note:
Feedback level detection compares PI2 Control Feedback from analog input
H3-xx = 26 [MFAI Function Selection = PI2 Control Feedback]
to these parameters:
•
S3-13 [PI2 Control Low Feedback Lvl]
for low feedback level detection
•
S3-15 [PI2 Control High Feedback Lvl]
for high feedback level detection
■
S3-18: PI2 Control Custom Unit 1
No.
(Hex.)
Name
Description
Default
(Range)
S3-18
(322B)
RUN
PI2 Control Custom Unit 1
Sets the first character of the PI2 Control custom unit display when
S3-04 = 49 [PI2 Control Unit
Selection = Custom(S3-18~20)]
.
41
(20 - 7A)
■
S3-19: PI2 Control Custom Unit 2
No.
(Hex.)
Name
Description
Default
(Range)
S3-19
(322C)
RUN
PI2 Control Custom Unit 2
Sets the second character of the PI2 Control custom unit display when
S3-04 = 49 [PI2 Control Unit
Selection = Custom(S3-18~20)]
.
41
(20 - 7A)
■
S3-20: PI2 Control Custom Unit 3
No.
(Hex.)
Name
Description
Default
(Range)
S3-20
(322D)
RUN
PI2 Control Custom Unit 3
Sets the third character of the PI2 Control custom unit display when
S3-04 = 49 [PI2 Control Unit
Selection = Custom(S3-18~20)]
.
41
(20 - 7A)
◆
S5: Hand/Off/Auto Operation
S5 parameters
set the drive operation in HAND, OFF, or AUTO Mode. The drive operation in each mode changes
when the
S5-04 [HAND-OFF-AUTO Behavior]
setting changes.
Table 5.58 Definitions of Each Mode
Operation Mode
Description
AUTO
The drive operates as specified by the frequency reference and Run command from the sources set in
b1-01 [Frequency Reference Selection 1]
and
b1-
02 [Run Command Selection 1]
.
HAND
The drive operates as specified by the frequency reference from the source set in
S5-01 [HAND Frequency Reference Source]
.
OFF
The drive is stopped and will not run until you activate the MFDI set for
H1-xx = AF or B0 [MFDI Function Selection = Emergency Override FWD or
REV]
. The drive uses the frequency reference source set in
b1-01
.
When
b1-02 = 0 [Keypad] to 3 [Option PCB]
, the MFDI set for
H1-xx = 12, 13, or 69 [Forward Jog, Reverse Jog, or Jog Run 2]
will also run the drive.
•
When
S5-01 = 1 [HAND Ref S5-05 or PID SP S5-06]
:
The drive operates as specified by the frequency reference set in
S5-05 [HAND Frequency Reference]
or PID
setpoint set in
S5-06 [HAND Setpoint]
.
•
When
S5-01 = 2 [Set by b1-01]
:
The drive operates as specified by the frequency reference from the source set in
b1-01
.
Parameter
S5-02 [HAND/AUTO Switchover During Run]
sets the drive to change between HAND and AUTO Modes
during run. When
S5-02 = 1 [Enabled]
and you pushed
or
, the drive will change between HAND and
AUTO Modes.
Note:
•
When
b1-02 = 1 [Digital Input] to 3
and the drive is running in HAND Mode,
will have no effect, regardless of the
S5-02
setting.
•
When
S5-04 = 1 [Normal]
, the drive will always be in AUTO Mode at power up.
•
When
S5-04 = 0 [Legacy]
, the power up state changes when
S5-10 [AUTO Key Memory at Power Down]
changes.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...