10.5 Metasys N2 Communications
732
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
–
Coast to Stop with
EF0
–
Emergency Stop with
EF0
•
Metasys N2 I/O
Three Metasys N2 outputs are used to select the desired behavior:
–
AO 21 - Cable Loss Timeout
–
AO 22 - Cable Loss Speed
–
BO 11 - Communication Fault
Table 10.13 Cable Loss Behavior Summary
Behavior
H5-04
[Communication Error Stop
Method]
Cable Loss Timeout
(AO 21)
Cable Loss Speed
(AO 22)
Communication Fault
Enable
(BO 11)
Decelerate to stop (stop time in
C1-02
) with
EF0
fault
0 [Ramp to Stop]
Timeout Interval
x
ON
Coast to stop with
EF0
fault
1 [Coast to Stop]
Timeout Interval
x
ON
Emergency stop (stop time in
C1-09
) with
EF0
fault
2 [Fast Stop (Use C1-09)]
Timeout Interval
x
ON
Continue at last speed
3 [Alarm Only]
0
x
x
Continue at last speed with alarm
3 [Alarm Only]
Timeout Interval
x
ON
Continue at preset speed with alarm
4 [Run at H5-34 (CE Go-To-Freq)]
Timeout Interval
Preset speed
ON
Note:
1. Communication must first be established and then lost for these features to function as described. If a bypass is powered-up without a
cable connected or with the master controller offline, a communications timeout does not occur.
2. For modes that describe the bypass running after a communications timeout, a Run command must have been issued (BO 1 =
“
ON
”
or BO
2 =
“
ON
”
) prior to loss of communications. For safety purposes, the bypass will not automatically restart from a stopped condition. If a
user requires the bypass to restart automatically, additional external wiring is required to accomplish this (consult factory).
Upon expiration of the communications timeout interval, the FAULT LED lights and remains lit until
communication is restored.
•
Continue at Last Speed
In this mode, Cable Loss Timeout (AO 21) is set to 0, disabling the cable loss feature. The other two settings Cable
Loss Speed (AO 22) and Communication Fault Enable (BO 11) are ignored. If communication is lost, the bypass
simply maintains its last commanded state. The bypass will not display an alarm or fault to indicate it has lost
communication. This behavior can also be achieved by setting
H5-04 = 3
. The bypass will display an alarm and
continue running. For this specific condition, the Communication Fault Enable (BO 11) must be enabled and Cable
Loss Timeout (AO 21) should be set to a value other than 0.
•
Continue at Preset Speed
In this mode, Cable Loss Timeout (AO 21) is set to the desired interval, Cable Loss Speed (AO 22) is set to the
desired preset speed and
H5-04 = 4
. If the time between messages exceeds the timeout interval, the drive speed
command (AO 1) is set to the Cable Loss Speed (AO 22) and the drive continues running at this new speed.
Communication Fault Enable (BO 11) must be set to
“
ON
”
.
•
Stop with Fault (EF0)
Communication Fault Enable (BO 11) must be set to
“
ON
”
. In this mode, Cable Loss Timeout (AO 21) is set to the
desired interval and parameter
H5-04 = 0, 1, or 2
. If the time between messages exceeds the timeout interval, the
bypass will declare a
CE
fault. The stopping method is determined by the setting of
H5-04
:
–
H5-04 = 0
selects Ramp to Stop. The deceleration time or the slope of the ramp is determined by
C1-02
–
H5-04 = 1
selects Coast to Stop. The bypass does not attempt to control the rate of deceleration.
–
H5-04 = 2
selects Emergency or Fast Stop. The deceleration time is determined by
C1-09
.
Note:
The behavior of the bypass at cable loss is controlled by
H5-04
. This parameter works with the points as described in the table above to
determine how the bypass will respond to a cable loss. If the cable loss fault is disabled, the bypass will continue in its last state, if running
the bypass will continue to run at the last commanded frequency.
◆
Communications Timing
To prevent overrun of the slave side, the master cannot send a message to the same drive for a selected length of time.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...