Z1-36: Loss of Load Bypass Det Time
No.
(Hex.)
Name
Description
Default
(Range)
Z1-36
(85E9)
Loss of Load Bypass Det
Time
The motor current must be equal to or less than this value to detect a loss of load.
1.0 s
(0.0 - 300.0 s)
■
Z1-39: Drive/Bypass Source Select
No.
(Hex.)
Name
Description
Default
(Range)
Z1-39
(85EC)
Drive/Bypass Source Select
Sets the function to select the Drive or the Bypass as the source of Drive/Bypass Mode selection.
0
(0 - 3)
0 : Keypad
The HOA keypad selects the Drive or Bypass as the source.
Drive/Bypass hotkeys work.
Z2-0x = 33
Drive/Bypass is disabled.
1 : Digital Input
Z2-xx
parameters select the Drive or Bypass as the source.
The Drive/Bypass hotkeys are disabled.
Z2-0x = 33
Drive/Bypass works.
2 : Serial Communications
The serial communications protocol selected in
H5-08
selects the Drive or Bypass as the source.
The hotkey and DI are disabled, Drive/Bypass by register 8400, bit 12 only (via BACNet, Modbus, P1, N2).
3 : Option PCB
The hotkey and DI are disabled, Drive/Bypass by register 8400, bit 12 only (via Option PCB).
■
Z1-40: Auto Transfer Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
Z1-40
(85ED)
Auto Transfer Delay Time
When you enable Auto Transfer and the bypass detects a drive fault, the bypass controller will wait
for the length of time set in this parameter before it switches to bypass.
0.0 s
(0.0 - 300.0 s)
■
Z1-42: Soft Starter Selection
No.
(Hex.)
Name
Description
Default
(Range)
Z1-42
(85EF)
Soft Starter Selection
Selects the soft starter device type when you use it with a bypass.
0
(0 - 2)
Note:
When
[Z1-42 = 1 or 2]
to enable the soft starter, the bypass automatically disables welded contactor detection. Parameter
Z1-55 [Welded
Contactor Detection]
does will not have an effect.
0 : Not Installed – Contactor Only
Turns off the cabinet fans (if equipped) when in Bypass Mode.
1 : Installed – Coast To Stop
Cabinet fans (if equipped) will run in both Drive and Bypass Modes.
2 : Installed – Ramp To Stop
Allows "Soft Start" and "Soft Stop" operation when the unit has a soft-starter. Additional wiring and configuration is
necessary for the soft-starter.
This setting disables Energy Savings Mode.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...