446
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
30: External Overload Motor 2 (NC)
Setting Value
Function
Description
30
External Overload Motor 2
(NC)
When input is open, it will trigger an
oL
fault and open bypass (K3) contactors.
31: HAND Select
Setting Value
Function
Description
31
HAND Select
The HAND function command will come from a digital input and the unit ignores the HAND key on the HOA operator.
If you set both HAND and AUTO functions to come from digital inputs, the HOA function will be OFF because both
inputs are not active. The OFF key on the HOA operator will always put the HOA function into the OFF state.
32: AUTO Select
Setting Value
Function
Description
32
AUTO Select
The AUTO function command will come from a digital input and the unit ignores the AUTO key on the HOA operator.
If you set both HAND and AUTO functions to come from digital inputs, the HOA function will be OFF because both
inputs are not active. The OFF key on the HOA operator will always put the HOA function into the OFF state.
33: Drive/Bypass Select
Setting Value
Function
Description
33
Drive/Bypass Select
The DRIVE/BYPASS select function command will come from a digital input, and the unit ignores the DRV/BYP key on the HOA
operator.
34: Fault Reset
Setting Value
Function
Description
34
Fault Reset
Resets any faults that are present.
Resets faults.
35: External Fault (EF0)
Setting Value
Function
Description
35
External Fault (EF0)
Issues external fault
EF0
from the bypass to the drive.
36: External Fault (EFB)
Setting Value
Function
Description
36
External Fault (EFB)
Triggers external fault
EFB
on the bypass.
37: Run Reverse (AUTO)
Setting Value
Function
Description
37
Run Reverse (AUTO)
Starts and stops the bypass in reverse.
38: Fire Stat Switch (NC)
Setting Value
Function
Description
38
Fire Stat Switch (NC)
Stops the drive from running and shows
“
Fire Stat
”
on the keypad.
39: Freeze Stat Switch (NC)
Setting Value
Function
Description
39
Freeze Stat Switch (NC)
Stops the drive from running and shows
“
Freeze Stat
”
on the keypad.
40: Smoke Alarm (NC)
Setting Value
Function
Description
40
Smoke Alarm (NC)
Stops the drive from running and shows
“
Smoke Alarm
”
on the keypad.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...