Y4-19: Differential Lvl Detection Time
No.
(Hex.)
Name
Description
Default
(Range)
Y4-19
(3D0C)
RUN
Differential Lvl Detection
Time
Sets the length of time that the difference between PID Feedback and the Differential Feedback must
be more than
Y4-18 [Differential Level]
before the drive will respond as specified by
Y4-20
[Differential Level Detection Selection]
.
10 s
(0 - 3600 s)
■
Y4-20: Differential Level Detection Sel
No.
(Hex.)
Name
Description
Default
(Range)
Y4-20
(3D0D)
RUN
Differential Level Detection
Sel
Sets the drive response during a Differential Level Detected condition.
0
(0 - 2)
0 : Fault (and Digital Out)
1 : Alarm (and Digital Out)
2 : Digital Out Only
■
Y4-22: Low City On-Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
Y4-22
(3D0F)
RUN
Low City On-Delay Time
Sets the length of time that the drive will wait to stop when the drive detects a Low City Pressure
condition.
10 s
(1 - 1000 s)
■
Y4-23: Low City Off-Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
Y4-23
(3D10)
RUN
Low City Off-Delay Time
Sets the length of time that the drive will wait to start again after you clear a Low City Pressure
condition.
5 s
(0 - 1000 s)
■
Y4-24: Low City Alarm Text
No.
(Hex.)
Name
Description
Default
(Range)
Y4-24
(3D11)
RUN
Low City Alarm Text
Sets the alarm message to show on the keypad when the drive detects a Low City Pressure condition.
0
(0 - 2)
0 : Low City Pressure
1 : Low Suction Pressure
2 : Low Water in Tank
■
Y4-36: Pressure Reached Exit Conditions
No.
(Hex.)
Name
Description
Default
(Range)
Y4-36
(3D1D)
RUN
Pressure Reached Exit
Conditions
Sets how the digital output responds to Feedback changes after it activates.
1
(0, 1)
0 : Hysteresis Above & Below
The terminal set for
H2-xx = 42 [MFDO Function Selection = Pressure Reached]
will deactivate when the Feedback
is less than the
“
Setpoint - Hysteresis
”
or more than the
“
Se Hysteresis
”
for the time set in
Y4-39 [Pressure
Reached Off Delay Time]
.
1 : Hysteresis 1-Way
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...