376
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
■
S1-02: Voltage Reduction Rate
No.
(Hex.)
Name
Description
Default
(Range)
S1-02
(3201)
Voltage Reduction Rate
Sets the rate at which the drive will decrease the output voltage as a percentage of the V/f pattern
when operating with no load.
50.0%
(50.0 - 100.0%)
■
S1-03: Voltage Restoration Level
No.
(Hex.)
Name
Description
Default
(Range)
S1-03
(3202)
Voltage Restoration Level
Sets the level at which the drive will start to restore the voltage as a percentage of the drive rated
torque.
20.0%
(0.0 - 90.0%)
■
S1-04: Voltage Restoration Off Level
No.
(Hex.)
Name
Description
Default
(Range)
S1-04
(3203)
Voltage Restoration Off
Level
Sets the level at which voltage restoration for the V/f pattern is complete as a percentage of the drive
rated torque. If the output is more than
S1-04
, the drive will control the voltage as specified by the V/
f pattern setting.
50.0%
(10.0 - 100.0%)
Note:
The lower limit of this parameter is the value of
S1-03 [Voltage Restoration Level]
+ 10.0%.
■
S1-05: Volt Restore Sensitivity Time K
No.
(Hex.)
Name
Description
Default
(Range)
S1-05
(3204)
Volt Restore Sensitivity
Time K
Sets the level of sensitivity of the output torque and LPF time constant for the voltage reduction rate.
You can adjust the level of sensitivity with the load response.
1.000 s
(0.000 - 3.000 s)
■
S1-06: Volt Restore Impact Load Time K
No.
(Hex.)
Name
Description
Default
(Range)
S1-06
(3205)
Volt Restore Impact Load
Time K
Sets the voltage restoration time constant when you add an impact load.
0.050 s
(0.000 - 1.000 s)
■
S1-07: Output Phase Loss Level
No.
(Hex.)
Name
Description
Default
(Range)
S1-07
(324C)
Output Phase Loss Level
Decreases the output phase loss level when Dynamic Noise control is active.
100.0%
(10.0 - 100.0%)
◆
S2: Sequence Run Timers
S2 parameters
set the programmable run timers for Real Time Clock (RTC). The timers set the drive to start and stop
automatically at specified times. You can set the timers to run daily, on weekdays, on weekends, or only on specific
days of the week.
■
Sequence Timer 1
When the current time reaches the
S2-01 [Timer 1 Start Time]
value, the drive will do the
S2-04 [Timer 1 Sequence
Selection]
action. When the current time reaches the
S2-02 [Timer 1 Stop Time]
value, the drive will stop the
S2-04
action. To use this function, set the current day in
S2-03 [Timer 1 Day Selection]
.
•
When
S2-04 = 0 [Digital Out Only]
or the terminal set for
H1-xx = 51 [MFDI Function Selection = Sequence
Timer Disable]
is active:
Sequence Timer 1 has no effect on the drive Run command. The drive starts correctly based on the status of the Run
command source set in
b1-02 [Run Command Selection 1]
.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...