10.6 MEMOBUS/Modbus Communications
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
751
Register No.
(Hex.)
Description
0009
MFDO setting
bit 0
Drive MFDO (terminal M1-M2)
1: ON, 0: OFF
bit 1
Drive MFDO (terminal M3-M4)
1: ON, 0: OFF
bit 2
Drive MFDO (terminal M5-M6)
1: ON, 0: OFF
bit 3 - 5
Region Code
bit 6
1: bit 7 function is enabled
bit 7
Fault relay output (terminal MA/MB-MC)
1: ON, 0: OFF
bit 8 - F
Region Code
000A - 000C
Reserved
000D
PI2 Control Setpoint
Units: 0.01%
Setting range: -100.00% to +100.00%
To enable this function, set MEMOBUS register 000F, bit 4 = 1.
000E
Reserved
000F
Command selection setting
bit 0
Reserved
bit 1
PID control target input
1: Enables target values from MEMOBUS/Modbus
bit 2
Torque reference/torque limit input
1: Enables setting values from MEMOBUS/Modbus
bit 3
Torque compensation input
1: Enables setting values from MEMOBUS/Modbus
bit 4
PI2 control target input
1: Enables setting values from MEMOBUS/Modbus
bit 5
PID feedback from the MEMOBUS/Modbus
1: Enables PID feedback (15FF (Hex.)) from MEMOBUS/Modbus
bit 6 - B
Reserved
bit C
Terminal S5 input for broadcast message
1: Enabled, 0: Disabled
bit D
Terminal S6 input for broadcast message
1: Enabled, 0: Disabled
bit E
Terminal S7 input for broadcast message
1: Enabled, 0: Disabled
bit F
Reserved
0010 - 001F
Reserved
15FF
PID Feedback over comms
3004
Time Setting
Setting range: 0000 to 2359 (decimal), the default value at energize: 0000
Sets the hour and the minute in HHMM format.
•
HH: 00 to 23 (decimal)
•
MM: 00 to 59 (decimal)
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...