SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
■
Z1-43: Soft Starter Delay Timer
No.
(Hex.)
Name
Description
Default
(Range)
Z1-43
(85F0)
Soft Starter Delay Timer
Sets the delay time between closing contactor K3 and energizing the soft starter.
2.0 s
(0.0 - 60.0 s)
■
Z1-44: Soft Starter Rampdown Timeout
No.
(Hex.)
Name
Description
Default
(Range)
Z1-44
(85F1)
Soft Starter Rampdown
Timeout
Sets the maximum wait time for the current to be less than 5% of
E2-01
after removing the soft
starter Run command.
15.0 s
(1.0 - 60.0 s)
■
Z1-50: Bypass Input Phase Loss Level
No.
(Hex.)
Name
Description
Default
(Range)
Z1-50
(85F7)
Bypass Input Phase Loss
Level
The bypass measures the current unbalance between phases to detect input phase loss.
25.0%
(5.0 - 50.0%)
Sets the current unbalance level between phases as a percentage of
E2-01
when operating in Bypass Mode. Use this
function with
Z1-51
to detect input or output phase loss during bypass operation.
The unbalance level is determined by measuring the RMS current in each of the output phases. The amount of current
unbalance between the phases is calculated using the this formula:
Unbalance Level = (I
(max)
- I
(min)
) / I
(max)
× 100%
When the unbalance level is more than
Z1-50
for longer than
Z1-51
, it triggers
FB15
–
Input Phase Loss
and the drive
coasts to stop.
■
Z1-51: Bypass Input Phase Loss Delay
No.
(Hex.)
Name
Description
Default
(Range)
Z1-51
(85F8)
Bypass Input Phase Loss
Delay
Sets the trip time for an input phase loss condition in Bypass Mode.
5.0 s
(0.0 - 30.0 s)
■
Z1-52: Input Phase Rotation Detection
No.
(Hex.)
Name
Description
Default
(Range)
Z1-52
(85F9)
Input Phase Rotation
Detection
Sets bypass response when the Bypass Mode phase rotation is incorrect.
0
(0 - 2)
The unit ignores input phase rotation when operating in Drive Mode. Input phase rotation determines motor direction
when operating in Bypass Mode.
If input phase rotation is reversed and
Z1-52 = 1
, when operation starts in Bypass Mode, it will trigger an
AL16
–
Input Phase Rotation
alarm and operation continues.
If input phase rotation is reversed and
Z1-52 = 2
, when operation starts in Bypass Mode, it will trigger an
FB16
–
Input Phase Rotation
fault and the drive will coast to stop.
Controls the behavior of the bypass phase rotation detection when operating in Bypass Mode.
0 : Disabled
1 : Alarm
2 : Fault
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...