648
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
S2-05
(320A)
Timer 1 Reference Source Selects the frequency reference source to run the drive when sequence timer 1 is active
(only applicable when
S2-04 > 0 [Timer 1 Sequence Selection ≠ Digital Out Only]
).
0 : Operator (d1-01/YA-01)
1 : Operator (d1-02/YA-02)
2 : Operator (d1-03/YA-03)
3 : Operator (d1-04/YA-04)
4 : Terminals
5 : Serial Com
6 : Option PCB
8 : Set by b1-01
Note:
For reference source 0 to 3, the drive will use
d1-xx
frequency reference when PID
mode is disabled and
YA-xx
setpoint when PID is enabled.
0
(0 - 8)
S2-06
(320B)
Timer 2 Start Time
Sets the start time for timer 2.
Note:
•
Default is when
o4-22 = 1 [Time Format = 12 Hour Clock]
. When
o4-22 = 0 [24
Hour Clock]
, default is 00:00. When
o4-22 = 2 [12 Hour JP Clock]
, default is 00:00
AM.
•
Range is when
o4-22 = 1
. When
o4-22 = 0
, range is 00:00 to 24:00. When
o4-22 =
2
, range is 00:00 AM to 11:59 PM.
12:00
(12:00 AM - 11:59 PM)
S2-07
(320C)
Timer 2 Stop Time
Sets the stop time for timer 2.
Note:
•
Default is when
o4-22 = 1 [Time Format = 12 Hour Clock]
. When
o4-22 = 0 [24
Hour Clock]
, default is 00:00. When
o4-22 = 2 [12 Hour JP Clock]
, default is 00:00
AM.
•
Range is when
o4-22 = 1
. When
o4-22 = 0
, range is 00:00 to 24:00. When
o4-22 =
2
, range is 00:00 AM to 11:59 PM.
12:00
(12:00 AM - 11:59 PM)
S2-08
(320D)
Timer 2 Day Selection
Sets the days for which sequence timer 2 is active.
0 : Timer disabled
1 : Daily
2 : Mon - Fri
3 : Sat - Sun
4 : Monday
5 : Tuesday
6 : Wednesday
7 : Thursday
8 : Friday
9 : Saturday
10 : Sunday
0
(0 - 10)
S2-09
(320E)
Timer 2 Sequence
Selection
Sets the drive response when sequence timer 2 is active.
0 : Digital Out Only
1 : Run
2 : Run - PID Disable
0
(0 - 2)
S2-10
(320F)
Timer 2 Reference Source Selects the frequency reference source to run the drive when sequence timer 2 is active
(only applicable when
S2-09 > 0 [Timer 2 Sequence Selection ≠ 0]
).
0 : Operator (d1-01/YA-01)
1 : Operator (d1-02/YA-02)
2 : Operator (d1-03/YA-03)
3 : Operator (d1-04/YA-04)
4 : Terminals
5 : Serial Com
6 : Option PCB
8 : Set by b1-01
Note:
For reference source 0 to 3, the drive will use
d1-xx
frequency reference when PID
mode is disabled and
YA-xx
setpoint when PID is enabled.
0
(0 - 8)
S2-11
(3210)
Timer 3 Start Time
Sets the start time for timer 3.
Note:
•
Default is when
o4-22 = 1 [Time Format = 12 Hour Clock]
. When
o4-22 = 0 [24
Hour Clock]
, default is 00:00. When
o4-22 = 2 [12 Hour JP Clock]
, default is 00:00
AM.
•
Range is when
o4-22 = 1
. When
o4-22 = 0
, range is 00:00 to 24:00. When
o4-22 =
2
, range is 00:00 AM to 11:59 PM.
12:00
(12:00 AM - 11:59 PM)
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...