YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
85
■
240 V Enclosed Wire Gauges and Torques
Table 3.7 Input Wiring
Model
H6BP
Standard Non-Fused
Input Disconnect Switch S1
With Option PM
Circuit Breaker CB1
Current Rating
Amps
AWG, kcmil
Tightening Torque
(in lb)
Current Rating
Amps
AWG, kcmil
Tightening Torque
(in lb)
A002
20
14-8
20
15
14-10 or 8-3/0
50 or 120
A003
20
14-8
20
15
14-10 or 8-3/0
50 or 120
A004
20
14-8
20
15
14-10 or 8-3/0
50 or 120
A006
20
14-8
20
20
14-10 or 8-3/0
50 or 120
A009
20
14-8
20
25
14-10 or 8-3/0
50 or 120
A015
20
14-8
20
35
14-10 or 8-3/0
50 or 120
A022
45
10, 8, or (6-2)
35, 40, or 50
50
14-10 or 8-3/0
50 or 120
A028
63
10, 8, or (6-2)
35, 40, or 50
70
14-10 or 8-3/0
50 or 120
A042
100
8-2/0
200
100
14-10 or 8-3/0
50 or 120
A054
100
8-2/0
200
125
14-10 or 8-3/0
50 or 120
A068
100
8-2/0
200
150
14-10 or 8-3/0
50 or 120
A080
115
8-2/0
200
150
14-10 or 8-3/0
50 or 120
A104
175
4-4/0
225
150
14-10 or 8-3/0
50 or 120
A130
250
3/0-350 kcmil
225
250
4-4/0
225
A154
250
3/0-350 kcmil
225
250
3/0-350
225
A192
250
3/0-350 kcmil
225
400
(1-2) x (2/0-500 kcmil)
(1-2) x 442
A248
400
(1-2) x (2/0-500 kcmil)
(1-2) x 442
600
(1-2) x (2/0-500 kcmil)
(1-2) x 442
Table 3.8 Output and Control Wiring
Model
H6BP
Motor Wiring
Standard Motor
Terminal Block TB1
Ground Wiring
Control Wiring
AWG,
kcmil
Tightening
Torque
(in lb)
AWG,
kcmil
Tightening
Torque
(in lb)
A1
Terminal Blocks
TB1, TB3-TB6
A1
Terminal Block
TB2 (FE)
A2
Terminal Blocks
TB1-TB4 and TB6
Panel
Terminal Block
TB4
AWG,
kcmil
Tightening
Torque
(in lb)
AWG,
kcmil
Tightening
Torque
(in lb)
AWG,
kcmil
Tightening
Torque
(in lb)
AWG,
kcmil
Tightening
Torque
(in lb)
A002
14-2
32
14-10, 8, 6-
4, or 2
35, 40, 45,
or 50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
A003
14-2
32
14-10, 8, 6-
4, or 2
35, 40, 45,
or 50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
A004
14-2
32
14-10, 8, 6-
4, or 2
35, 40, 45,
or 50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
A006
14-2
32
14-10, 8, 6-
4, or 2
35, 40, 45,
or 50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
A009
14-2
32
14-10, 8, 6-
4, or 2
35, 40, 45,
or 50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
A015
14-2
32
14-10, 8, 6-
4, or 2
35, 40, 45,
or 50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
A022
14-2
32
14-10, 8, 6-
4, or 2
35, 40, 45,
or 50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
A028
14-2
32
14-10, 8, 6-
4, or 2
35, 40, 45,
or 50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
A042
14-2
32
14-10, 8, 6-
4, or 2
35, 40, 45,
or 50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
A054
14-2
32
14-10, 8, 6-
4, or 2
35, 40, 45,
or 50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...