YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
275
Setting Value
Function
Reference
72
High PI2 Control Feedback Level
89
Output Current Lim
94
Loss of Prime
95
Thermostat Fault
96
High Feedback
97
Low Feedback
9E
Low PI Auxiliary Control Level
9F
High PI Auxiliary Control Level
A9
RELAY Operator Control
AB
Thrust Mode
AC
Setpoint Not Maintained
B2
BAS Interlock
B8
Pump Fault
B9
Transducer Loss
Setting Value
Function
Reference
BA
PI Auxiliary Control Active
BB
Differential Feedback Exceeded
BC
Sleep Active
BD
Start Delay
BE
Pre-Charge
C0
HAND Mode
C1
AUTO Mode
C2
OFF Mode
C3
Main Feedback Lost
C4
Backup Feedback Lost
100 to 1C4
Inverse Outputs of 0 to C4
Sets an inverse output of the function for the MFDO.
Put a 1 at the front of the function setting to set inverse
output. For example, set
138
for inverse output of
38
[Drive Enabled]
.
*1
Inverse output is not available.
*2
You cannot set this parameter on models D169 to D273, A154 to A248, and B065 to B302.
■
Extended MFDO1 to MFDO3 Function Selection
You can set MFDO functions to
bit 0 to bit 2 [MEMOBUS MFDO1 to 3]
of MEMOBUS register 15E0 (Hex.). Use
H2-40 to H2-42 [Mbus Reg 15E0h bit0 to bit2 Output Func]
to select the function.
Figure 5.43 Functional Block Diagram of MEMOBUS Multi-function Output
Table 5.41 MEMOBUS MFDO Registers
Register number
(Hex.)
Name
15E0
bit0
MEMOBUS MFDO 1
bit1
MEMOBUS MFDO 2
bit2
MEMOBUS MFDO 3
Note:
•
Refer to
MFDO Setting Values on page 280
for more information about MFDO setting values.
•
When you do not set functions to
H2-40 to H2-42
, set them to
F
.
■
Output of Logical Operation Results of MFDO
This enables the logical operation results of two MFDOs to be output to one MFDO terminal.
Use
H2-60, H2-63, and H2-66 [Term M1-M2 Secondary Function to Term M5-M6 Secondary Function]
to set the
function of the output signal for which logical operations are performed.
Use
H2-61, H2-64, H2-67 [Term M1-M2 Logical Operation to Term M5-M6 Logical Operation]
to set the logical
operation.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...