662
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
YF-03
(3F52)
RUN
PI Aux Control Setpoint
Sets the level to which the drive will try to regulate.
Note:
Parameters
YF-21 [PI Aux Ctrl Level Unit Selection]
and
YF-22 [PI Aux Level
Decimal Place Pos]
set the unit and resolution.
20.0 PSI
(0.0 - 6000.0)
YF-04
(3F53)
RUN
PI Aux Control Minimum
Level
Sets the level below which the drive must be for longer than
YF-05 [PI Aux Control Sleep
Delay Time]
before the drive goes to sleep and turns off all lag pumps.
Note:
•
Set this parameter to 0.0 to disable the function.
•
Parameters
YF-21 [PI Aux Ctrl Level Unit Selection]
and
YF-22 [PI Aux Level
Decimal Place Pos]
set the unit and resolution.
10.0 PSI
(0.0 - 6000.0)
YF-05
(3F54)
RUN
PI Aux Control Sleep
Delay Time
Sets the length of time that the drive will delay before it goes to sleep after the level is less
than
YF-04 [PI Aux Control Minimum Level]
(when
YF-23 = 1 [PI Aux Ctrl Output Level
Select = Inverse Acting]
) or more than
YF-24 [PI Auxiliary Ctrl Maximum Level]
(when
YF-23 = 0 [Direct Acting]
).
5 s
(0 - 3600 s)
YF-06
(3F55)
RUN
PI Aux Control Wake-up
Level
Sets the level to wake up the drive when the drive after
YF-04 [PI Aux Control Minimum
Level]
or
YF-24 [PI Auxiliary Ctrl Maximum Level]
put the drive to sleep.
Note:
•
Parameter
YF-23 [PI Aux Ctrl Output Level Select]
sets the condition to wake up the
drive.
–
YF-23 = 0 [Direct Acting]
: The PI Aux Feedback must be less than the level set in
this parameter for longer than the time set in
YF-07
to wake up.
–
YF-23 = 1 [Inverse Acting]
: The PI Aux Feedback must be more than the level set
in this parameter for longer than the time set in
YF-07 [PI Aux Control Wake-up
Time]
to wake up.
•
Parameters
YF-21 [PI Aux Ctrl Level Unit Selection]
and
YF-22 [PI Aux Level
Decimal Place Pos]
set the unit and resolution.
30.0 PSI
(-999.9 - +999.9 PSI)
YF-07
(3F56)
PI Aux Control Wake-up
Time
Sets the time to wake up the drive when the drive after
YF-04 [PI Aux Control Minimum
Level]
or
YF-24 [PI Auxiliary Ctrl Maximum Level]
put the drive to sleep.
Note:
Parameter
YF-23 [PI Aux Ctrl Output Level Select]
sets the condition to wake up the
drive.
•
YF-23 = 0 [Direct Acting]
: The PI Aux Feedback must be less than the level set in
YF-06
for longer than the time set in
YF-07
to wake up.
•
YF-23 = 1 [Inverse Acting]
: The PI Aux Feedback must be more than the level set in
YF-06 [PI Aux Control Wake-up Level]
for longer than the time set in
YF-07
to wake
up.
1 s
(0 - 3600 s)
YF-08
(3F57)
RUN
PI Aux Control Minimum
Speed
Sets the minimum speed at which the drive can run when the PI Auxiliary Control has an
effect on the output speed.
Note:
The drive will use
Y1-06 [Minimum Speed]
and
Y4-12 [Thrust Frequency]
as the
minimum speed when PI Aux Control does not have an effect on the output speed or
when you set
YF-08 < Y1-06 and Y4-12
.
0.00 Hz
(0.00 - 400.00 Hz)
YF-09
(3F58)
RUN
PI Aux Control Low
Level Detect
Sets the level below which the drive must be for longer than
YF-10 [PI Aux Control Low
Lvl Det Time]
to respond as specified by
YF-11 [PI Aux Control Low Level Det Sel]
.
Note:
•
Set this parameter to 0.0 to disable the function.
•
Parameter
YF-10
only applies to when
YF-11 = 2 and 3 [Fault and Auto-Restart
(time set by YF-15)]
.
•
Parameters
YF-21 [PI Aux Ctrl Level Unit Selection]
and
YF-22 [PI Aux Level
Decimal Place Pos]
set the unit and resolution.
0.0 PSI
(-999.9 - +999.9 PSI)
YF-10
(3F59)
RUN
PI Aux Low Level
Detection Time
Sets the length of time that the PI Aux Feedback must be less than
YF-09 [PI Aux Control
Low Lvl Detection]
to trigger a drive response when
YF-11 = 2 and 3 [PI Aux Control Low
Level Det Sel = Fault and Auto-Restart (time set by YF-15)]
.
0.1 s
(0.0 - 300.0 s)
YF-11
(3F5A)
PI Aux Control Low
Level Det Sel
Sets drive response when the PI Aux Feedback decreases to less than
YF-09 [PI Aux
Control Low Lvl Detection]
for longer than
YF-10 [PI Aux Control Low Lvl Det Time]
.
0 : No Display
1 : Alarm Only
2 : Fault
3 : Auto-Restart (time set by YF-15)
Note:
•
Set
YF-01 = 1 [PI Aux Control Selection = Enabled]
and
YF-09 [PI Aux Control
Low Level Detect]
> 0 to enable PI Aux Low Level Detection.
•
Parameter
YF-10
only applies when
YF-11 = 2 or 3
.
1
(0 - 3)
YF-12
(3F5B)
RUN
PI Aux Control High
Level Detect
Sets the value above which the level must be for longer than
YF-13 [PI Aux High Level
Detection Time]
to respond as specified by
YF-14 [PI Aux Hi Level Detection Select]
.
Note:
•
Set this parameter to 0.0 to disable the function.
•
Parameter
YF-13
only applies to when
YF-14 = 2 and 3 [Fault and Auto-Restart
(time set by YF-15)]
.
•
Parameters
YF-21 [PI Aux Ctrl Level Unit Selection]
and
YF-22 [PI Aux Level
Decimal Place Pos]
set the unit and resolution.
0.0 PSI
(-999.9 - +999.9 PSI)
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...