616
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
H1-76
(39F0)
RUN
Terminal S6 Off-Delay
Time
Sets the length of time necessary for Terminal S6 to be open before the drive removes the
programmed function.
0.00 s
(0.00 - 300.00 s)
H1-77
(39F1)
RUN
Terminal S7 Off-Delay
Time
Sets the length of time necessary for Terminal S7 to be open before the drive removes the
programmed function.
0.00 s
(0.00 - 300.00 s)
■
H1-xx: MFDI Setting Values
Setting Value
Function
Description
Ref.
3
Multi-Step Speed
Reference 1
Uses speed references
d1-01 to d1-08
to set a multi-step speed reference.
4
Multi-Step Speed
Reference 2
Uses speed references
d1-01 to d1-08
to set a multi-step speed reference.
5
Multi-Step Speed
Reference 3
Uses speed references
d1-01 to d1-08
to set a multi-step speed reference.
6
Jog Reference Selection
Sets the drive to use the JOG Frequency Reference (JOG command) set in
d1-17 [Jog Reference]
. The JOG Frequency
Reference (JOG command) overrides the
d1-01 to d1-08 [References 1 to 8]
settings.
7
Accel/Decel Time
Selection 1
Sets the drive to use
Acceleration/Deceleration Time 1 [C1-01, C1-02]
or
Acceleration/Deceleration Time 2 [C1-03,
C1-04]
.
8
Baseblock Command (N.
O.)
Sets the command that stops drive output and coasts the motor to stop when the input is ON.
ON : Baseblock (drive output stop)
OFF : Normal operation
9
Baseblock Command (N.
C.)
Sets the command that stops drive output and coasts the motor to stop when the input terminal is OFF.
ON : Normal operation
OFF : Baseblock (drive output stop)
A
Accel/Decel Ramp Hold
Momentarily pauses motor acceleration and deceleration when the terminal is turned ON, retains the output frequency
that was stored in the drive at the time of the pause, and restarts motor operation.
B
Overheat Alarm (oH2)
Sets the drive to display an
oH2 [Drive Overheat Warning]
alarm when the input terminal is ON. The alarm does not
have an effect on drive operation.
C
Analog Terminal Enable
Selection
Sets the command that enables or disables the terminals selected in
H3-14 [Analog Input Terminal Enable Sel]
.
ON : Input to the terminal selected with
H3-14
is enabled
OFF : Input to the terminal selected with
H3-14
is disabled
F
Not Used
Use this setting for unused terminals or to use terminals in through mode.
14
Fault Reset
Sets the command to reset the current fault when the Run command is inactive.
Note:
The drive ignores the fault reset command when the Run command is active. Remove the Run command before
trying to reset a fault.
15
Fast Stop (N.O.)
Sets the command to ramp to stop in the deceleration time set in
C1-09 [Fast Stop Time]
when the input terminal is
activated while the drive is operating.
17
Fast Stop (N.C.)
Sets the command to ramp to stop in the deceleration time set in
C1-09 [Fast Stop Time]
when the input terminal is
activated while the drive is operating.
18
Timer Function
Sets the command to start the timer function. Use this setting with
Timer Output [H2-xx = 12]
.
19
PID Disable
Sets the command to disable PID control when
b5-01 = 1 or 3 [PID Mode Setting = Standard or Fref + PID Trim]
.
ON : PID control disabled
OFF : PID control enabled
1B
Programming Lockout
Sets the command to prevent parameter changes when the terminal is OFF.
ON : Programming Lockout
OFF : Parameter Write Prohibit
1E
Reference Sample Hold
Sets the command to sample the frequency reference at terminals A1 or A2 and hold the frequency reference at that
frequency.
20
External Fault (NO-
Always-Ramp)
When the terminal activates, the drive ramps to stop in the selected deceleration time. Fault relay output terminal MA-
MC will turn ON, and MB-MC will turn OFF. The drive always detects external faults whether the drive is stopped or
running.
21
External Fault (NC-
Always-Ramp)
When the terminal deactivates, the drive ramps to stop in the selected deceleration time. Fault relay output terminal
MA-MC will turn ON, and MB-MC will turn OFF. The drive always detects external faults whether the drive is
stopped or running.
22
External Fault (NO-
@Run-Ramp)
When the terminal activates during run, the drive ramps to stop in the selected deceleration time. Fault relay output
terminal MA-MC will turn ON, and MB-MC will turn OFF. The drive does not detect external faults while the drive is
stopped.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...