YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
405
5.12
T: Auto-Tuning
T parameters
set input data for Induction Motor Auto-Tuning.
◆
T0: Tuning Mode Selection
■
T0-00: Tuning Mode Selection
No.
(Hex.)
Name
Description
Default
(Range)
T0-00
(1197)
Tuning Mode Selection
Sets the type of Auto-Tuning.
0
(0)
0 : Motor Parameter Tuning
◆
T1: Induction Motor Auto-Tuning
T1 parameters
set the Auto-Tuning input data for induction motor tuning.
Note:
•
The base frequency of drive-dedicated motors and special vector-control motors can be lower than the base frequency of general-purpose
motors, which is 50 Hz or 60 Hz. In these conditions, the drive uses the lower frequency as the value for
E1-06 [Base Frequency]
and
E1-
04 [Maximum Output Frequency]
after Auto-Tuning completes. If the maximum output frequency is too low and causes problems, change
the setting of
E1-04
after Auto-Tuning completes.
•
The drive automatically sets these induction motor parameters:
–
E1-xx [V/f Pattern for Motor 1]
–
E2-xx [Motor Parameters]
■
T1-01: Auto-Tuning Mode Selection
No.
(Hex.)
Name
Description
Default
(Range)
T1-01
(0701)
Auto-Tuning Mode Selection Sets the type of Auto-Tuning.
0
(0, 2)
0 : Rotational Auto-Tuning
2 : Stationary Line-Line Resistance
■
T1-02: Motor Rated Power
No.
(Hex.)
Name
Description
Default
(Range)
T1-02
(0702)
Motor Rated Power
Uses the units set in
o1-58 [Motor Power Unit Selection]
to set the motor rated output power.
Determined by o2-04
(0.00 - 650.00 HP)
■
T1-03: Motor Rated Voltage
No.
(Hex.)
Name
Description
Default
(Range)
T1-03
(0703)
Motor Rated Voltage
Sets the rated voltage (V) of the motor. Enter the base speed voltage for constant output motors.
Determined by o2-04
(208/240 V: 0.0 - 255.5 V,
480 V: 0.0 - 511.0 V)
If you do Auto-Tuning on a drive-dedicated motor or a special vector-control motor, the voltage or frequency can be
lower than a general-purpose motor. Always compare the data from the nameplate or test report with the Auto-Tuning
results and check for differences. Enter the voltage necessary to operate the motor in no-load conditions at rated speed
for better control precision around rated speed. If the motor test report or the motor nameplate is not available, enter
approximately 90% of the motor rated voltage.
If the drive input power supply voltage is low, enter approximately 90% of the input voltage. When the input power
supply voltage is low, the current will increase. Make sure that the main power supply capacity is correct and use a
molded-case circuit breaker for the drive.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...