Table 5.62 AUTO Run Command Behavior when b1-01 = 7 to 9
AUTO Command
External Run
(Terminal, Serial, or Option)
AUTO LED
Drive Operation
Description
HOA State
No
No
OFF
No
•
Drive Stopped
•
Drive is in OFF Mode
OFF
Yes
No
OFF
No
•
Drive is in AUTO Mode
•
Waiting for Run command
AUTO
No
Yes
OFF
No
•
Drive received the Run command
•
Waiting for AUTO command
OFF
Yes
Yes
ON
Yes
Drive is operating in AUTO Mode
AUTO
Yes
Yes
Long Blink
(50% duty)
No
•
Drive is in Sleep Mode
•
Output Frequency is 0 or drive
decelerates to STOP
AUTO
Yes
Yes
Double Blink
No
Waiting for cycle of commands
Example:
•
Drive Ready condition was removed
•
Drive starts Fast-Stop operation
AUTO
*1
The LED is available when
o2-24 ≠ 2 [LED Light Function Selection ≠ Keypad LED Light Disable]
.
By default, the drive will energize in AUTO Mode. When you de-energize the drive in AUTO Mode while
S5-10 = 1
[AUTO Key Memory at Power Down = Enabled]
, the drive will memorize the
press and it will energize in
AUTO Mode again. When you de-energize the drive in HAND or OFF Mode, the drive will energize in OFF Mode.
Note:
If you set
b1-02 = 0 [Run Command Selection 1 = Keypad]
and
S5-10 = 2 [AUTO Mode]
at the same time, the drive detects
oPE05 [Run
Cmd/Freq Ref Source Sel Err]
.
■
HAND Command
You can input the HAND Command from:
•
when
S5-07 = 1 [Operation HAND Key = Enabled]
•
One of MFDI terminals set for:
–
H1-xx = 6E [HAND Command]
–
H1-xx = 6D [AUTO Command]
when
S5-04 = 0 [HAND-OFF-AUTO Behavior = Legacy]
When
S5-04 = 0
, the drive will receive the HAND Command when the MFDI set for
H1-xx = 6E
is activated, or
when the MFDI set for
H1-xx = 6D
is OFF and the drive receives a Run command.
Note:
The drive will disable
when
o2-02 = 0 [OFF Key Function Selection = Disabled]
and
b1-02 ≠ 0 [Run Command Selection 1 ≠
Keypad]
.
HAND Command
External Run
(Terminal, Serial, or
Option)
HAND LED
Drive Operation
HOA Mode
Description
HOA State
No
No
OFF
No
Normal
Legacy
•
Drive Stopped
•
Drive is in OFF Mode
OFF
Yes
No
OFF
No
Legacy
HAND Mode ready but No Run
command
HAND
Yes
Yes
ON
Yes
Legacy
Drive is operating in HAND Mode
HAND
Yes
Yes
Long Blink
(50% duty)
No
Legacy
Output Frequency is 0 or drive
decelerates to STOP
HAND
Yes
Yes
Double Blink
No
Legacy
Waiting for cycle of commands
Example:
•
Drive Ready condition was
removed
•
Drive starts Fast-Stop operation
HAND
Yes
Yes/No
ON
Yes
Normal
Drive is operating in HAND Mode
HAND
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...