440
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Note:
When
Z1-42 = 1 or 2 [Soft Starter Selection = Installed
–
Coast To Stop or Installed
–
Ramp To Stop]
, the bypass will automatically disable
welded contactor detection.
This detection is active when you take the bypass out of bypass run mode or when you first apply power to the bypass
package.
The bypass will trigger
FB18 - Welded Bypass Contactor Detected
when it detects this condition. Cycle power to the
bypass package to clear this fault.
■
Z1-56: Test Mode
No.
(Hex.)
Name
Description
Default
(Range)
Z1-56
(85FD)
RUN
Test Mode
Sets the behavior of the drive input contactor K1 during Bypass Mode.
0
(0, 1)
0 : Drive Power Off during Bypass
In a 3-contactor bypass configuration, this setting, when the bypass system switches to Bypass Mode, contactor K1
opens and the HV600 drive disconnects from incoming power. When the bypass system switches to Drive mode,
contactor K1 closes and the HV600 drive can operate.
1 : Drive Power On during Bypass
Contactor K1 stays closed in Drive Mode and Bypass Mode. This setting will keep the status ring active or to
decrease the length of time that for the drive to start operating when the system switches from Bypass Mode to Drive
Mode.
■
Z1-60: Blackout Operation Select
No.
(Hex.)
Name
Description
Default
(Range)
Z1-60
(8601)
Blackout Operation Select
Sets bypass behavior when contactor voltage is less than
Z1-19 [Blackout Voltage Level]
.
1
(0 - 3)
0 : Fault
1 : Restart Delay with Speed Search
2 : Restart Delay from Zero Speed
3 : Disabled
■
Z1-61: Power Loss Restart Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
Z1-61
(8602)
Power Loss Restart Delay
Time
Sets the time delay for restart.
10 s
(1 - 300 s)
■
Z1-70: Green Contactor Mode
No.
(Hex.)
Name
Description
Default
(Range)
Z1-70
(860B)
Green Contactor Mode
Green Contactor Mode opens the output and motor contactors when the bypass unit is idle.
0
(0, 1)
0 : Disabled
1 : Enabled
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...