YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
229
Figure 5.30 S-Curve Timing Diagram - Forward/Reverse Operation
Note:
•
Setting the S-curve will increase the acceleration and deceleration times.
■
C2-01: S-Curve Time @ Start of Accel
No.
(Hex.)
Name
Description
Default
(Range)
C2-01
(020B)
S-Curve Time @ Start of
Accel
Sets the S-curve acceleration time at start.
0.20 s
(0.00 - 10.00 s)
■
C2-02: S-Curve Time @ End of Accel
No.
(Hex.)
Name
Description
Default
(Range)
C2-02
(020C)
S-Curve Time @ End of
Accel
Sets the S-curve acceleration time at completion.
0.20 s
(0.00 - 10.00 s)
■
C2-03: S-Curve Time @ Start of Decel
No.
(Hex.)
Name
Description
Default
(Range)
C2-03
(020D)
S-Curve Time @ Start of
Decel
Sets the S-curve deceleration time at start.
0.20 s
(0.00 - 10.00 s)
■
C2-04: S-Curve Time @ End of Decel
No.
(Hex.)
Name
Description
Default
(Range)
C2-04
(020E)
S-Curve Time @ End of
Decel
Sets the S-curve deceleration time at completion.
0.00 s
(0.00 - 10.00 s)
◆
C3: Slip Compensation
The Slip Compensation function improves the speed accuracy of an induction motor. As loads on induction motors
increase, motor slip increases and motor speed decreases. By adjusting the output frequency in accordance with the
motor load, it compensates the slip and makes the motor speed equal to the frequency reference.
■
C3-01: Slip Compensation Gain
No.
(Hex.)
Name
Description
Default
(Range)
C3-01
(020F)
RUN
Slip Compensation Gain
Sets the gain for the slip compensation function. Usually it is not necessary to change this setting.
0.0
(0.0 - 2.5)
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...