YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
227
5.3
C: Tuning
C parameters
adjust drive operation, including:
•
Acceleration Time
•
Deceleration Time
•
Slip Compensation
•
Torque Compensation
•
Carrier Frequency
◆
C1: Accel & Decel Time
You can set two different acceleration and deceleration time pairs in the drive. When you activate and deactivate
H1-
xx = 7 [MFDI Function Selection = Accel/Decel Time Selection]
, you can switch acceleration and deceleration times
during run.
Acceleration time parameters always set the time to accelerate from 0 Hz to
E1-04 [Maximum Output Frequency]
.
Deceleration time parameters always set the time to decelerate from
E1-04
to 0 Hz.
C1-01 [Acceleration Time 1]
and
C1-02 [Deceleration Time 1]
are the default active accel/decel settings.
Parameter
Range
C1-01 [Acceleration Time 1]
0.1 to 6000.0 s
C1-02 [Deceleration Time 1]
C1-03 [Acceleration Time 2]
C1-04 [Deceleration Time 2]
■
Use MFDIs to Switch Acceleration Times
shows the different acceleration and deceleration times.
Table 5.29 Accel/Decel Times and Active Parameters
H1-xx = 7
[Accel/Decel Time Selection 1]
Active Parameter
Acceleration Time
Deceleration Time
OFF
C1-01 [Acceleration Time 1]
C1-02 [Deceleration Time 1]
ON
C1-03 [Acceleration Time 2]
C1-04 [Deceleration Time 2]
shows an operation example to change acceleration and deceleration times. It is necessary to set
b1-03 =
0 [Stopping Method Selection = Ramp to Stop]
for this example.
C1-01: Acceleration Time 1
C1-02: Deceleration Time 1
C1-03: Acceleration Time 2
C1-04: Deceleration Time 2
H1-xx = 7: Accel/Decel Time Selection 1
Figure 5.29 Timing Diagram of Acceleration and Deceleration Times
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...