YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
343
■
L8-05: Input Phase Loss Protection Sel
No.
(Hex.)
Name
Description
Default
(Range)
L8-05
(04B1)
Input Phase Loss Protection
Sel
Sets the function to enable and disable input phase loss detection.
1
(0, 1)
0 : Disable
1 : Enabled
The drive measures ripples in DC bus voltage to detect input phase loss.
The drive detects phase loss when power supply phase loss occurs or the main circuit capacitor becomes unusable,
which causes
PF [Input Phase Loss]
to show on the keypad.
Disable the detection of the input power supply phase loss function in these conditions:
•
During deceleration
•
The run command is not input
•
The output current is less than 30% of the drive rated current.
■
L8-07: Output Phase Loss Protection Sel
No.
(Hex.)
Name
Description
Default
(Range)
L8-07
(04B3)
Output Phase Loss
Protection Sel
Sets the function to enable and disable output phase loss detection. The drive starts output phase loss
detection when the output current decreases to less than 5% of the drive rated current.
1
Note:
The drive can incorrectly start output phase loss detection when the motor rated current is very small compared to the drive rating.
0 : Disabled
1 : Fault when one phase is lost
If the drive loses one output phase, it will trigger
LF [Output Phase Loss]
.
The output turns off and the motor coasts to stop.
2 : Fault when two phases are lost
If the drive loses more than one output phase, it will trigger
LF [Output Phase Loss]
.
The output turns off and the motor coasts to stop.
■
L8-09: Output Ground Fault Detection
No.
(Hex.)
Name
Description
Default
(Range)
L8-09
(04B5)
Output Ground Fault
Detection
Sets the function to enable and disable ground fault protection.
Determined by o2-04
(0, 1)
0 : Disable
The drive will not detect ground faults.
1 : Enabled
If there is high leakage current or a ground short circuit in one or two output phases, the drive will detect
GF [Ground
Fault]
.
Note:
If the ground path impedance is low, the drive can detect
oC [Overcurrent]
,
SC [Out Short Circuit or IGBT Fault]
, or
ov [DC Bus
Overvoltage]
instead of
GF
.
■
L8-10: Heatsink Fan Operation Selection
No.
(Hex.)
Name
Description
Default
(Range)
L8-10
(04B6)
Heatsink Fan Operation
Selection
Sets operation of the heatsink cooling fan.
0
(0 - 2)
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...