544
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Bypass Model
Drive Model
Rated Current (A)
2 kHz
5 kHz
8 kHz
10 kHz
12.5 kHz
A154
2169
169
169
135.2
112.7
-
A192
2211
211
211
168.8
140.7
-
A248
2273
273
273
218.4
182
-
■
480 V Models
Table 7.24 Carrier Frequency and Rated Current Derating
Bypass Model
Drive Model
Rated Current (A)
2 kHz
5 kHz
8 kHz
10 kHz
12.5 kHz
B001 to B004
4005
4.8
4.8
4.0
3.5
2.9
B007
4008
7.6
7.6
6.4
5.6
4.6
B011
4011
11.0
11.0
9.2
8.1
6.6
B014
4014
14.0
14.0
11.8
10.3
8.4
B021
4021
21.0
21.0
17.6
15.4
12.6
B027
4027
27.0
27.0
22.7
19.8
16.2
B034
4034
34.0
34.0
28.6
24.9
20.4
B040
4040
40.0
40.0
33.6
29.3
24.0
B052
4052
52.0
52.0
43.7
38.1
31.2
B065
4065
65.0
65.0
54.6
47.7
39.0
B077
4077
77.0
77.0
64.7
56.5
46.2
B096
4096
96.0
96.0
80.6
70.4
57.6
B124
4124
124
124
99.2
92.7
-
B156
4156
156
156
124.8
104
-
B180
4180
180
180
144
120
-
B240
4240
240
224
176
144
-
B302
4302
302
281.9
221.5
181.2
-
◆
Derating Depending on Ambient Temperature
When you install drives in a place where ambient temperatures are higher than the rated conditions or install drives
side-by-side in the enclosure panel, set
L8-12 [Ambient Temperature]
and
L8-35 [Installation Method Selection]
.
Derate the output current as specified in
to
No.
(Hex.)
Name
Description
Default
(Range)
L8-12
(04B8)
Ambient Temperature
Setting
Sets the ambient temperature of the drive installation area.
40 °C
(Determined by L8-35)
No.
(Hex.)
Name
Description
Default
(Range)
L8-35
(04EC)
Installation Method
Selection
Sets the type of drive installation.
2
(0 - 3)
Note:
The drive will detect an
oPE02 [Parameter Range Setting Error]
in these conditions:
•
If you set
L8-12 = 60 °C
and
L8-35 = 1 or 3
for models 2011 to 2114 and 4005 to 4124
•
If you set
L8-35 = 1 or 3
for models 2143 to 2273 and 4156 to 4302
0 : IP20/UL Open Type
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...