YF-01: PI Aux Control Selection
No.
(Hex.)
Name
Description
Default
(Range)
YF-01
(3F50)
PI Aux Control Selection
Sets the PI Auxiliary Control function.
0
(0, 1)
0 : Disabled
1 : Enabled
•
A staged Lead drive will de-stage when
U5-16 [PI Aux Ctrl Feedback]
is less than
YF-04 [PI Aux Control
Minimum Level]
for the time set in
YF-05 [PI Aux Control Sleep Delay Time]
.
•
A staged Lead drive will de-stage when
U5-16
is more than
YF-24 [PI Auxiliary Ctrl Maximum Level]
for the time
set in
YF-05
.
■
YF-02: PI Aux Control Transducer Scale
No.
(Hex.)
Name
Description
Default
(Range)
YF-02
(3F51)
RUN
PI Aux Control Transducer
Scale
Sets the full scale (10 V or 20 mA) output of the pressure transducer connected to the analog input
terminal programmed for
H3-xx = 27 [PI Aux Control Feedback Level]
.
145.0
(1.0 - 6000.0)
Note:
Parameters
YF-21 [PI Aux Ctrl Level Unit Selection]
and
YF-22 [PI Aux Level Decimal Place Pos]
set the unit and resolution.
■
YF-03: PI Aux Control Setpoint
No.
(Hex.)
Name
Description
Default
(Range)
YF-03
(3F52)
RUN
PI Aux Control Setpoint
Sets the level to which the drive will try to regulate.
20.0 PSI
(0.0 - 6000.0)
Note:
Parameters
YF-21 [PI Aux Ctrl Level Unit Selection]
and
YF-22 [PI Aux Level Decimal Place Pos]
set the unit and resolution.
■
YF-04: PI Aux Control Minimum Level
No.
(Hex.)
Name
Description
Default
(Range)
YF-04
(3F53)
RUN
PI Aux Control Minimum
Level
Sets the level below which the drive must be for longer than
YF-05 [PI Aux Control Sleep Delay
Time]
before the drive goes to sleep and turns off all lag pumps.
10.0 PSI
(0.0 - 6000.0)
Note:
•
Set this parameter to 0.0 to disable the function.
•
Parameters
YF-21 [PI Aux Ctrl Level Unit Selection]
and
YF-22 [PI Aux Level Decimal Place Pos]
set the unit and resolution.
■
YF-05: PI Aux Control Sleep Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
YF-05
(3F54)
RUN
PI Aux Control Sleep Delay
Time
Sets the length of time that the drive will delay before it goes to sleep after the level is less than
YF-
04 [PI Aux Control Minimum Level]
(when
YF-23 = 1 [PI Aux Ctrl Output Level Select = Inverse
Acting]
) or more than
YF-24 [PI Auxiliary Ctrl Maximum Level]
(when
YF-23 = 0 [Direct Acting]
).
5 s
(0 - 3600 s)
■
YF-06: PI Aux Control Wake-up Level
No.
(Hex.)
Name
Description
Default
(Range)
YF-06
(3F55)
RUN
PI Aux Control Wake-up
Level
Sets the level to wake up the drive when the drive after
YF-04 [PI Aux Control Minimum Level]
or
YF-24 [PI Auxiliary Ctrl Maximum Level]
put the drive to sleep.
30.0 PSI
(-999.9 - +999.9 PSI)
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...