228
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
■
C1-01: Acceleration Time 1
No.
(Hex.)
Name
Description
Default
(Range)
C1-01
(0200)
RUN
Acceleration Time 1
Sets the length of time to accelerate from zero to maximum output frequency.
30.0 s
(0.1 - 6000.0 s)
■
C1-02: Deceleration Time 1
No.
(Hex.)
Name
Description
Default
(Range)
C1-02
(0201)
RUN
Deceleration Time 1
Sets the length of time to decelerate from maximum output frequency to zero.
30.0 s
(0.1 - 6000.0 s)
■
C1-03: Acceleration Time 2
No.
(Hex.)
Name
Description
Default
(Range)
C1-03
(0202)
RUN
Acceleration Time 2
Sets the length of time to accelerate from zero to maximum output frequency.
30.0 s
(0.1 - 6000.0 s)
■
C1-04: Deceleration Time 2
No.
(Hex.)
Name
Description
Default
(Range)
C1-04
(0203)
RUN
Deceleration Time 2
Sets the length of time to decelerate from maximum output frequency to zero.
30.0 s
(0.1 - 6000.0 s)
■
C1-09: Fast Stop Time
No.
(Hex.)
Name
Description
Default
(Range)
C1-09
(0208)
RUN
Fast Stop Time
Sets the length of time that the drive will decelerate to zero for a Fast Stop.
10.0 s
(0.1 - 6000.0 s)
These conditions will start the Fast Stop function:
•
When the drive received the Fast Stop command from the MFDI terminal
•
When you set
Fast Stop (Use C1-09)
for a parameter to set a stopping method when the drive detected a fault
Set
H1-xx = 15, 17 [MFDI Function Selection = Fast Stop (N.O.), Fast Stop (N.C.)]
.
When the drive receives the Fast Stop command, the motor ramps to stop in the deceleration time set in
C1-09
. After
the drive receives the Fast Stop command, you cannot start the drive operation again until deceleration is complete.
To clear the Fast Stop condition, deactivate the Fast Stop command, deactivate the Run command, then activate the
Run command again.
The terminal set for
H2-xx = 4C [MFDO Function Selection = During Fast Stop]
will activate during Fast Stop.
Note:
If you decelerate the drive too quickly, the drive will detect an
ov [Overvoltage]
fault and shut off the output, and the motor will coast to
stop. To prevent motor coasting and stop the motor quickly and safely, make sure to set a Fast Stop time in
C1-09
.
◆
C2: S-Curve Characteristics
Use S-curve characteristics to smooth acceleration and deceleration and to minimize abrupt shock to the load.
Set S-curve characteristic time during acceleration/deceleration at start and acceleration/deceleration at stop.
The following figure explains how S-curves are applied.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...