9.13 o: Keypad-Related Settings
644
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
◆
o2: Keypad Operation
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
o2-02
(0506)
OFF Key Function
Selection
Sets the function to use
on the keypad to stop the drive when the Run command
source for the drive is REMOTE (external) and not assigned to the keypad.
0 : Disabled
1 : Enabled
1
(0, 1)
o2-03
(0507)
User Parameter Default
Value
Sets the function to keep the settings of changed parameters as user parameter defaults to
use during initialization.
0 : No change
1 : Set defaults
2 : Clear all
0
(0 - 2)
o2-04
(0508)
Drive Model (KVA)
Selection
Sets the Drive Model code. Set this parameter after you replace the control board.
Determined by the drive
(-)
o2-05
(0509)
Home Mode Freq Ref
Entry Mode
Sets the function that makes it necessary to push
to use the keypad to change the
frequency reference value while in Drive Mode.
0 : ENTER Key Required
1 : Immediate / MOP-style
0
(0, 1)
o2-06
(050A)
Keypad Disconnect
Detection
Sets the function that stops the drive if you disconnect the keypad connection cable from
the drive or if you damage the cable while the keypad is the Run command source.
0 : Disabled
1 : Enabled
1
(0, 1)
o2-09
(050D)
Reserved
-
-
o2-19
(061F)
Parameter Write during
Uv
Enables and disables the function to change parameter settings during a
Uv [DC Bus
Undervoltage]
condition.
0 : Disabled
1 : Enabled
0
(0, 1)
o2-24
(11FE)
LED Light Function
Selection
Sets the function to show the LED status rings and keypad LED lamps.
Note:
When you use
A1-03 [Initialize Parameters]
to initialize the drive, the drive will not
reset this parameter.
0 : Enable Status Ring & Keypad LED
1 : LED Status Ring Disable
2 : Keypad LED Light Disable
0
(0 - 2)
o2-27
(1565)
bCE Detection Selection
Sets drive operation if the Bluetooth device is disconnected when you operate the drive in
Bluetooth Mode.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use
C1-09
)
3 : Alarm Only
4 : No Alarm Display
3
(0 - 4)
◆
o3: Copy Keypad Function
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
o3-01
(0515)
Copy Keypad Function
Selection
Sets the function that saves and copies drive parameters to a different drive with the
keypad.
0 : Copy Select
1 : Backup (drive → keypad)
2 : Restore (keypad → drive)
3 : Verify (check for mismatch)
4 : Erase (backup data of keypad)
0
(0 - 4)
o3-02
(0516)
Copy Allowed Selection
Sets the copy function when
o3-01 = 1 [Copy Keypad Function Selection = Backup (drive
→ keypad)]
.
0 : Disabled
1 : Enabled
0
(0, 1)
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...