5.10 o: Keypad-Related Settings
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
363
To start the drive again after you push
to stop operation, turn the external Run command OFF and ON again.
■
o2-03: User Parameter Default Value
No.
(Hex.)
Name
Description
Default
(Range)
o2-03
(0507)
User Parameter Default
Value
Sets the function to keep the settings of changed parameters as user parameter defaults to use during
initialization.
0
(0 - 2)
When you set
o2-03 = 1 [Set defaults]
, the drive saves changed parameter settings as user parameter setting values in
a part of the memory that is isolated from drive parameters.
When you set
A1-03 = 1110 [Initialize Parameters = User Initialization]
to initialize the drive, the drive resets the
internal parameter setting values to those user parameter setting values.
0 : No change
1 : Set defaults
Saves changed parameter setting values as user default settings.
Set
o2-03 = 1
then push
to save the user parameter setting values. After the drive saves the setting value,
o2-03
automatically resets to
0
.
2 : Clear all
Deletes all of the saved user parameter setting values.
Set
o2-03 = 2
then push
to clear the user parameter setting values. The drive will automatically reset
o2-03
to
0
. If
you delete the user parameter setting values, you cannot set
A1-03 = 1110
to initialize parameters.
■
o2-04: Drive Model (KVA) Selection
No.
(Hex.)
Name
Description
Default
(Range)
o2-04
(0508)
Drive Model (KVA)
Selection
Sets the Drive Model code. Set this parameter after you replace the control board.
Determined by the drive
(-)
NOTICE:
Set o2-04 [Drive Model Selection] correctly. If you set this parameter incorrectly, it will decrease drive performance, cause
the protection function to operate incorrectly, and cause damage to the drive.
Note:
When the setting value of
o2-04
changes, related parameter setting values also change. Refer to
Defaults by Bypass and Drive Model on page
for more information.
These tables list the relation between
o2-04
setting values and drive models.
o2-04 Setting
Drive Model
65
2011
67
2017
68
2024
6A
2031
6B
2046
6D
2059
6E
2075
6F
2088
70
2114
72
2143
73
2169
74
2211
75
2273
o2-04 Setting
Drive Model
95
4005
97
4008
99
4011
9A
4014
9B
4021
9D
4027
9E
4034
9F
4040
A0
4052
A2
4065
A3
4077
A4
4096
A5
4124
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...