background image

1592025930 XEV23D GB r1.0 07.10.2011.doc

XEV23D

1/4

XEV23D

DRIVER FOR STEPPER ELECTRONIC EXPANSION

VALVES

--- MANUAL FOR RELEASE 1.2 ---

1.

GENERAL WARNING.........................................................................................................................1

2.

GENERAL DESCRIPTION..................................................................................................................1

3.

WIRING CONNECTIONS ...................................................................................................................1

4.

VALVE CONNECTIONS AND CONFIGURATION.............................................................................1

5.

ABSOLUTE MAXIMUM POWER........................................................................................................1

6.

FRONT PANEL ...................................................................................................................................2

7.

USER INTERFACE.............................................................................................................................2

8.

PARAMETER LIST .............................................................................................................................2

9.

DIGITAL INPUTS ................................................................................................................................3

10. FORCED OPENING............................................................................................................................3

11. ELECTRICAL CONNECTIONS...........................................................................................................3

12. RS485 SERIAL LINE...........................................................................................................................3

13. HOW TO: USE THE HOT-KEY...........................................................................................................3

14. DISPLAY MESSAGES........................................................................................................................4

15. TECHNICAL DATA..............................................................................................................................4

16. STANDARD VALUES .........................................................................................................................4

1. GENERAL WARNING

1.1 PLEASE READ BEFORE USING THIS MANUAL

This manual is part of the product and should be kept near the instrument for easy and quick

reference.

The instrument shall not be used for purposes different from those described hereunder. It cannot

be used as a safety device.

Check the application limits before proceeding.

1.2

SAFETY PRECAUTIONS

Check the supply voltage is correct before connecting the instrument.

Do not expose to water or moisture: use the controller only within the operating limits avoiding

sudden temperature changes with high atmospheric humidity to prevent formation of condensation

Warning:

disconnect all electrical connections before any kind of maintenance.

Fit the probe where it is not accessible by the End User. The instrument must not be opened.

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.r.l.”

(see address) with a detailed description of the fault.

Consider the maximum current which can be applied to each relay (see Technical Data).

Ensure that the wires for probes, loads and the power supply are separated and far enough from

each other, without crossing or intertwining.

In  case  of  applications  in  industrial  environments,  the  use  of  mains  filters  (our  mod.  FT1)  in

parallel with inductive loads could be useful.

2. GENERAL DESCRIPTION

The

XEV23D

module is able to drive a large variety of

stepper electronic expansion valves

. XEV23D

permits to regulate the superheat (SH) of the fluid that runs into refrigerating unit in order to obtain

optimized performance and a functioning of the evaporator independent by climatic or load conditions.

XEV23D

modules are equipped with two probe inputs, one for 4 to 20mA or 0 to 5V pressure transducer

and another one for NTC-EU or NTC-US temperature probe. There are also two configurable digital

inputs, the first one is free of voltage and the other

ones is free of voltage

to pass from the chilling to

the  heat-pump  model. With  the  useful  display  it’s  possible  to  see  the  value  of superheat (SH),  the

degree of opening of the valve or the probe values, the local keyboard allows to program the instrument

without any other devices. To complete instrument equipment, a RS485 serial link permits to connect

XEV23D to dIXEL monitoring and supervising systems.

3. WIRING CONNECTIONS

The  superheat  regulation  is  performed  only  when  the  cooling  digital  input  is  enabled. The following

scheme shows how the device takes the request of cooling:

Please  see  the  following  scheme  to  make  the  right  wirings.  With  "First  Level"  are  indicated  the

connections on the floor of the 4 DIN module and, of course, with "Second Level" the connections of the

1st floor that are only for the stepper motor of the valve and for HOT-KEY.

4. VALVE CONNECTIONS AND CONFIGURATION

WARNINGS

1. To avoid possible problems, before connecting the valve configure the driver by making the

right changes on the parameters. Select the kind of motor (

tEU parameter

) and check if the

valve is present in

tEP parameter table

reported here below.

2. The max distance between an XM controller and a valve

must not exceed 10 m

. To avoid

any problems, use only

shielded cables

with section greater than or equal to 0.325 mm²

(AWG22).

tEP

Model

LSt

(steps*10)

uSt

(steps*10)

CPP

(mA*10)

CHd

(mA*10)

Sr

(step/s)

0

Manual settings

Par

Par

Par

Par

Par

1

Alco EX4-EX5-EX6

5

75

50

10

500

2

Alco EX7

10

160

75

25

500

3

Alco EX8 500

10

260

80

50

500

4

Danfoss ETS-25/50

7

262

10

10

300

5

Danfoss ETS-100

10

353

10

10

300

6

Danfoss ETS-250/400

11

381

10

10

300

7

Sporlan SEI 0.5-11

0

159

16

5

200

8

Sporlan SER 1.5-20

0

159

12

5

200

9

Sporlan SEI 30

0

319

16

5

200

10

Sporlan SER(I) G,J,K

0

250

12

5

200

11

Sporlan SEI 50

0

638

16

5

200

12

Sporlan SEH(I) 100

0

638

16

5

200

13

Sporlan SEH(I) 175

0

638

16

5

200

If you can see your valve on the table, please select the valve through

tEP parameter.

In this way, you

can be sure of a right configuration.

About  the  connection,  please  pay  attention  to  the  following  table  to  have  a  quick  reference  on  the

connection mode for valves of different manufacturer. In any case,

the unique and valid reference has

to be considered the datasheet made by manufacturer of the valve

:

4 WIRES VALVES (BIPOLAR)

Connection

numbering

ALCO EX

SPORLAN

SEI-SEH

DANFOSS

ETS

4

BLUE

WHITE

BLACK

2

BROWN

BLACK

WHITE

3

BLACK

RED

RED

1

WHITE

GREEN

GREEN

5-6 WIRES VALVES (UNIPOLAR)

Connection

numbering

SPORLAN

SAGINOMIYA

4

ORANGE

ORANGE

2

RED

RED

3

YELLOW

YELLOW

1

BLACK

BLACK

5 – Common

GRAY

GRAY

AFTER MAKING THE CONNECTION, PLEASE SWITCH OFF AND ON THE XEV CONTROLLER IN

ORDER TO BE SURE OF THE RIGHT POSITIONING OF THE VALVE.

5. ABSOLUTE MAXIMUM POWER

XEV23D

is  able  to  drive  a  wide  range  of  stepper  valves,  in  the  following  table  are  indicated  the

maximum values of current that the actuator can supply to the stepper wiring. The dIXEL transformer to

use is the

TF20D

.

Содержание Dixell XEV23D

Страница 1: ... the probe values the local keyboard allows to program the instrument without any other devices To complete instrument equipment a RS485 serial link permits to connect XEV23D to dIXEL monitoring and supervising systems 3 WIRING CONNECTIONS The superheat regulation is performed only when the cooling digital input is enabled The following scheme shows how the device takes the request of cooling Plea...

Страница 2: ...n if the device cannot calculate superheat the valve can work at PEo percentage PEd Probe Error delay before stopping regulation 0 to 239sec 240 On unlimited if probe error duration is higher than PEd valve will close completely and Pf message will be showed With PEd on valve opening is PEo until probe error finishes tEU Type of Stepper motor UP bP it permits to select the kind of valve UP 5 6 wir...

Страница 3: ...rmits to increase integral time when SH is below the set point If FrC 0 fast recovery function is disabled DISPLAY Lod Local display SH PEr P1 P2 SH superheat PEr valve opening percentage P1 value of temperature measured P2 pressure measured by P2 probe CF Temperature measurement units C F C Celsius degree F Fahrenheit degree NOTE by changing measurement unit the regulation parameters have to be c...

Страница 4: ...se only bipolar valves 0 to 100 10mA 0 Pr1 oPE Start opening Percentage 0 to 100 85 Pr1 SFd Start Function duration 0 0 to 42min 00s res 10s 1 3 Pr1 MnF Maximum opening percentage 0 to 100 100 Pr1 FoP Forced Opening time out 0 to 100 nU nu Pr1 PI PARAMETERS trained staff Pb Proportional band chiller mode 0 1 to 50 0 C 1 to 90 F 10 0 Pr1 rS Band Offset 12 0 to 12 0 C 21 to 21 F 0 0 Pr1 inC Integrat...

Отзывы: