1592025930 XEV23D GB r1.0 07.10.2011.doc

XEV23D

2/4

NOTE:

the electrical power absorption of the valve can be unrelated to refrigeration power that valve

has.  Before  using  the  actuator,  please  read  the  technical  manual  of  the  valve  supplied  by  the

manufacturer and check the maximum current used to drive the valve in order to verify that they are

lower than those indicated below.

VA

LV

E

TY

PE

BIPOLAR VALVES

(4 wires)

Maximum Current 0.9A

UNIPOLAR VALVES

(5-6 wires)

Maximum Current 0.33A

6. FRONT PANEL

To display and to modify the set point.

In  programming  mode  it  selects  a

parameter or it confirms a value.

By pressing and releasing this key, it’s

possible  to  see  the  values  of the

probes.

In  programming  mode  it  slides  the

codes  of  the  parameters  or  it

increases their values.

In  programming  mode  it  slides  the

codes  of  parameters  or  it  decreases

their values.

KEYS COMBINATIONS

+

To lock or to unlock

the keyboard

+

To enter

programming mode.

6.1 XEV23D LEDS

On display there are some luminous dots. Their meaning is described in the following table:

LED

MODE

Function

ON

Low pressure alarm

ON

Maximum Operating Pressure alarm

OFF

Valve is completely closed

BLINKING

Valve is moving

ON

Valve is completely opened

BLINKING

Serial communication present

OFF

Serial communication absent

ON

Superheat alarm

7. USER INTERFACE

7.1 HOW TO: SEE THE READ-ONLY VALUES

1) Press and release

UP

button.

2) First read-only label is showed;

3) Brows parameter labels with

UP

or

DOWN

buttons.

4) Press

SET

to see read-only value. To change parameter, press

SET

.

5) To leave the fast access menu, press and release

SET+UP

or wait for time-out to expire (about 3

minutes).

7.2 HOW TO: SEE THE SET POINT

1) Press the

SET

buttons until the set point will be showed.

2) To come back to see temperature, wait about 5s or press newly

SET

key.

7.3 HOW TO: MODIFY THE SET POINT

To change the set point value operate as follows:

1)

Press the

SET

button until the set point will be showed.

2)

Use

UP

or

DOWN

buttons to change its value.

3)

Press

SET

button to store the new value.

7.4 HOW TO: ENTERING “PR1” PARAMETER MENU

To enter in “Pr1” level menu:

1) Pressing

SET

+

DOWN

buttons for about 3 seconds.

2) Instruments shows first parameter in Pr1 menu

7.5 HOW TO: ENTERING “PR2” PARAMETER MENU

To enter  to “Pr2” parameters list:

1.

Enter to “Pr1”.

2.

Select “Pr2” parameter and press

SET

.

3.

The “

PAS

” label will be shown, then “

0--

” with

0 blinking.

4.

Insert “

321

” password  through

UP

and

DOWN

buttons

,

then press

SET

to confirm.

7.6 HOW TO: CHANGE A PARAMETERS VALUE

To  change  the  parameter’s  value  operate  as

follows:

1.

Enter the Programming mode by pressing

the Set and

DOWN

button for about 3s.

2.

Select the required parameter.

3.

Press the

SET

button to display the value.

4.

Use

UP

or

DOWN

to change the value.

5.

Press

SET

to store the new value and move to the following parameter.

To exit: Press

SET + UP

or wait 30s without pressing any button.

NOTE

: the set value is stored even when the procedure is exited by waiting the time-out to expire.

8. PARAMETER LIST

NOTE: All pressure parameters are relatives or absolutes depending on the PrM parameter

REGULATION

SEt

SH Set point in Chill mode

(0,0 ÷ 24,0°C - 0 ÷ 43 °F)

St2

SH Set point in Heat Pump mode

(0,0 ÷ 24,0°C - 0 ÷ 43 °F)

FtY

Kind of gas:

(R22, 134, 404, 407, 410, 507, CO2) type of gas used by plant. This is a

fundamental parameter for correct functioning of all system.

PEo

Probe Error opening percentage:

(0 to 100%) if a temporary probe error occurs, valve

opening  percentage  is

PEo

until

PEd

time  is  elapsed.  If

PEO

is  different  from  0  it

assures  cooling  also  with  probe  error,  because  even  if  the  device  cannot  calculate

superheat the valve can work at

PEo

percentage.

PEd

Probe  Error  delay  before  stopping  regulation:

(0 to 239sec; 240=On=unlimited)  if

probe error duration is higher than

PEd,

valve will close completely and “

Pf

” message

will be showed. With

PEd=on

, valve opening is

PEo

until probe error finishes.

tEU

Type of Stepper motor:

(UP; bP) it permits to select the kind of valve.

UP

= 5-6 wires

unipolar  valves;

bP

=  4 wires  bipolar  valves.

!!!!!  WARNING  !!!!!

by  changing  this

parameter the valve has to be reinitialized.

tEP

Predefined valve selection:

(0 to 13) if

tEP=0

the user has to modify all the parameters

of configuration in order to use the valve. If

tEP

is different from 0 the device performs a

fast configuration of the following parameters:

LSt

,

USt

,

Sr

,

CPP

,

CHd

. To select the

right number please read the following table:

tEP

Model

LSt

(steps*10)

uSt

(steps*10)

CPP

(mA*10)

CHd

(mA*10)

Sr

(step/s)

0

Manual settings

Par

Par

Par

Par

Par

1

Alco EX4-EX5-EX6

5

75

50

10

500

2

Alco EX7

10

160

75

25

500

3

Alco EX8 500

10

260

80

50

500

4

Danfoss ETS-25/50

7

262

10

10

300

5

Danfoss ETS-100

10

353

10

10

300

6

Danfoss ETS-250/400

11

381

10

10

300

7

Sporlan SEI 0.5-11

0

159

16

5

200

8

Sporlan SER 1.5-20

0

159

12

5

200

9

Sporlan SEI 30

0

319

16

5

200

10

Sporlan SER(I) G,J,K

0

250

12

5

200

11

Sporlan SEI 50

0

638

16

5

200

12

Sporlan SEH(I) 100

0

638

16

5

200

13

Sporlan SEH(I) 175

0

638

16

5

200

If

tEP

is different from 0, previous configuration of

LSt

,

uSt

,

Sr

,

CPP

and

CHd

will be overwritten.

HFS

Kind of motor movement:

(HAF; FUL)

HAF

= half step. Use this setting for the unipolar valve.

FUL

= half step. Use this setting for the bipolar valve.

LSt

Minimum number of steps:

(0 to USt (*10)) it permits to select the minimum number of

steps. At this number of steps the valve should be closed. So it’s necessary the reading

of manufacturer datasheet to set correctly this parameter. It’s the minimum number of

steps to stay in advised range of functioning.

!!!!! WARNING !!!!! after changing this

parameter  the  valve will  have to  be  reinitialized.  The device  performs this

procedure  automatically  and  restarts its  normal  functioning  when  the

programming mode ends.

USt

Maximum number of steps:

(LSt to 800 (*10)) it permits to select the maximum number

of  steps.  At  this  number  of  steps  the  valve  should  be  completely  opened.  Read  the

datasheet provided by manufacturer of the valve to set correctly this parameter. It’s the

maximum number of steps to stay in advised range of functioning.

!!!!! WARNING !!!!!

after changing  this  parameter  the  valve will have to be reinitialized. The device

performs this procedure automatically and restarts its normal functioning when

the programming mode ends.

ESt

Extra  step  in  closing  phase:

(0 to 255 (*10)) it  sets  the  number of extra steps the

controller performs, when the valve is closed at start up, to force the closure of the valve.

Sr

Step rate:

(10 to 600 step/sec) it is the maximum speed to change step without losing

precision (=losing steps). It’s advised to stay under the maximum speed.

CPP

Current per phase (only bipolar valves):

(0 to 100 (*10mA)) it is the maximum current

per phase used to drive valve. It’s used

only with bipolar valves.

CHd

Holding current per phase (only bipolar valves):

(0 to 100 (*10mA)) it is the current

per  phase when  the  valve  is  stopped  for  more  than  4  minutes.  It’s  used

only  with

bipolar valves.

oPE

Start opening Percentage:

(0 to 100%) opening valve percentage when start function is

active and during post defrost phase. This phase duration is

SFd time

.

SFd

Start Function duration:

(0.0 to 42min 00s, res. 10s) it sets start function duration and

post-defrost duration.

During this phase the alarms are neglected.

MnF

Maximum opening percentage at normal Functioning:

(0 to 100%) during regulation

it sets the maximum valve opening percentage.

Содержание Dixell XEV23D

Страница 1: ... the probe values the local keyboard allows to program the instrument without any other devices To complete instrument equipment a RS485 serial link permits to connect XEV23D to dIXEL monitoring and supervising systems 3 WIRING CONNECTIONS The superheat regulation is performed only when the cooling digital input is enabled The following scheme shows how the device takes the request of cooling Plea...

Страница 2: ...n if the device cannot calculate superheat the valve can work at PEo percentage PEd Probe Error delay before stopping regulation 0 to 239sec 240 On unlimited if probe error duration is higher than PEd valve will close completely and Pf message will be showed With PEd on valve opening is PEo until probe error finishes tEU Type of Stepper motor UP bP it permits to select the kind of valve UP 5 6 wir...

Страница 3: ...rmits to increase integral time when SH is below the set point If FrC 0 fast recovery function is disabled DISPLAY Lod Local display SH PEr P1 P2 SH superheat PEr valve opening percentage P1 value of temperature measured P2 pressure measured by P2 probe CF Temperature measurement units C F C Celsius degree F Fahrenheit degree NOTE by changing measurement unit the regulation parameters have to be c...

Страница 4: ...se only bipolar valves 0 to 100 10mA 0 Pr1 oPE Start opening Percentage 0 to 100 85 Pr1 SFd Start Function duration 0 0 to 42min 00s res 10s 1 3 Pr1 MnF Maximum opening percentage 0 to 100 100 Pr1 FoP Forced Opening time out 0 to 100 nU nu Pr1 PI PARAMETERS trained staff Pb Proportional band chiller mode 0 1 to 50 0 C 1 to 90 F 10 0 Pr1 rS Band Offset 12 0 to 12 0 C 21 to 21 F 0 0 Pr1 inC Integrat...

Отзывы: