YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
301
Figure 5.62 Stall Prevention Level during Run with Analog Input
■
9: Output Frequency Lower Limit
Setting Value
Function
Description
9
Output Frequency Lower
Limit
Enters a signal to adjust the output frequency lower limit level as a percentage of the maximum output frequency.
■
B: PID Feedback
Setting Value
Function
Description
B
PID Feedback
Enter the PID feedback value as a percentage of the maximum output frequency.
When you use this function, set
b5-01 ≠ 0 [PID Mode Setting ≠ Disabled]
.
■
C: PID Setpoint
Setting Value
Function
Description
C
PID Setpoint
Enters the PID setpoint as a percentage of the maximum output frequency.
When you use this function, set
b5-01 ≠ 0 [PID Mode Setting ≠ Disabled]
.
Note:
Configuring this function disables the frequency reference set with
b1-01 [Frequency Reference Selection 1]
.
■
D: Frequency Bias
Setting Value
Function
Description
D
Frequency Bias
Enters the bias value added to the frequency reference as a percentage of the maximum output frequency.
The drive adds the input value from the MFAI terminal set with this function to the frequency reference as the bias
value.
Note:
When you select
d1-01 to d1-17 [Reference 1 to 8 or JOG Frequency Reference]
as the frequency reference, it will disable this function.
■
E: Motor Temperature (PTC Input)
Setting Value
Function
Description
E
Motor Temperature (PTC
Input)
Uses the motor Positive Temperature Coefficient (PTC) thermistor to prevent heat damage to the motor as a percentage of the
current value when the 10 V analog signal is input.
•
You can use the Positive Temperature Coefficient (PTC) thermistor as an auxiliary or alternative detection function
for
oL1 [Motor Overload]
problems to help prevent heat damage to motors. If the PTC input signal is more than the
overload alarm level,
oH3 [Motor Overheat (PTC Input)]
will flash on the keypad.
•
When the drive detects
oH3
, the motor stops with the setting in
L1-03
. When the drive detects
oH4
, the motor stops
with the setting in
L1-04
. When the drive incorrectly detects motor overheating problems, set
L1-05
.
■
F: Not Used
Setting Value
Function
Description
F
Not Used
Use this setting for unused terminals or to use terminals in through mode.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...