SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
347
5.9
n: Special Adjustment
n parameters
set these functions:
•
Function to prevent hunting
•
High-slip braking
•
Fine-tune the parameters that adjust motor control
◆
n1: Hunting Prevention
The Hunting Prevention function will not let low inertia or operation with a light load cause hunting. Hunting
frequently occurs when you have a high carrier frequency and an output frequency less than 30 Hz.
■
n1-01: Hunting Prevention Selection
No.
(Hex.)
Name
Description
Default
(Range)
n1-01
(0580)
Hunting Prevention
Selection
Sets the function to prevent hunting.
1
(0, 1)
When drive response is more important than the decrease of motor vibration, disable this function.
If hunting occurs, or if you use a high carrier frequency or Swing PWM, set this parameter to 2 for better hunting
prevention.
0 : Disabled
1 : Enabled (Normal)
■
n1-02: Hunting Prevention Gain Setting
No.
(Hex.)
Name
Description
Default
(Range)
n1-02
(0581)
Expert
Hunting Prevention Gain
Setting
Sets the performance of the hunting prevention function. Usually it is not necessary to change this
parameter.
1.00
(0.00 - 2.50)
Adjust this parameter in these conditions:
•
When
n1-01 = 1, 2 [Hunting Prevention Selection = Enabled (Normal), Enabled (High Carrier Frequency)]
: If
oscillation occurs when you operate a motor with a light load, increase the setting value in 0.1-unit increments.
•
When
n1-01 = 1, 2
, if the motor stalls: Decrease the setting value in 0.1-unit increments.
■
n1-03: Hunting Prevention Time Constant
No.
(Hex.)
Name
Description
Default
(Range)
n1-03
(0582)
Expert
Hunting Prevention Time
Constant
Sets the primary delay time constant of the hunting prevention function. Usually it is not necessary to
change this parameter.
Determined by o2-04
(0 - 500 ms)
Adjust this parameter in these conditions:
•
Load inertia is large: Increase the setting value. If the setting value is too high, response will be slower. Also, there
will be oscillation when the frequency is low.
•
Oscillation occurs at low frequencies: Decrease the setting value.
■
n1-05: Hunting Prevent Gain in Reverse
No.
(Hex.)
Name
Description
Default
(Range)
n1-05
(0530)
Expert
Hunting Prevent Gain in
Reverse
Sets the performance of the hunting prevention function. This parameter adjusts Reverse run. Usually
it is not necessary to change this parameter.
0.00
(0.00 - 2.50)
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...