6.12 Troubleshooting Without Fault Display
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
523
◆
oPE02 Error Occurs When Decreasing the Motor Rated Current Setting
Causes
Possible Solutions
Motor rated current and the motor no-load current setting in the drive are
incorrect.
•
You are trying to set the motor rated current in
E2-01 [Motor Rated Current (FLA)]
to a value
lower than the no-load current set in
E2-03 [Motor No-Load Current]
.
•
Make sure that value set in
E2-01
is higher than
E2-03
.
•
If it is necessary to set
E2-01
lower than
E2-03
, first decrease the value set to
E2-03
, then change
the
E2-01
setting as necessary.
◆
The Motor Stalls during Acceleration or Accel/Decel Time Is Too Long
Causes
Possible Solutions
The drive and motor system reached the torque limit or current suppression will
not let the drive accelerate.
•
Decrease the load.
•
Use a larger motor.
Note:
Although the drive has a Stall Prevention function and a Torque Compensation Limit function,
accelerating too fast or trying to drive a load that is too large can exceed the limits of the motor.
Torque limit is set incorrectly.
Set the torque limit correctly.
The acceleration time setting is too short.
Examine the values set in
C1-01 or C1-03 [Acceleration Times]
and set them to applicable values.
The load is too heavy.
•
Increase the acceleration time.
•
Examine the mechanical brake and make sure that it is fully releasing.
•
Decrease the load to make sure that the output current stays less than the motor rated current.
•
Use a larger motor.
Note:
•
In extruder and mixer applications, the load can increase as the temperature decreases.
•
Although the drive has a Stall Prevention function and a Torque Compensation Limit function,
accelerating too fast or trying to drive a load that is too large can exceed the limits of the motor.
The frequency reference is low.
•
Examine
E1-04 [Maximum Output Frequency]
and increase the setting if it is set too low.
•
Examine
U1-01 [Frequency Reference]
for the correct frequency reference.
•
Examine the multi-function input terminals to see if a frequency reference signal switch has been
set.
•
Examine the low gain level set in
H3-03, H3-11 [Terminal A1, A2 Gain Setting]
when you use
MFAI.
The frequency reference is set incorrectly.
When
H3-02, H3-10 = 1 [MFAI Function Selection = Frequency Gain]
are set, see if voltage
(current) has been set.
•
Check the values set in
H3-02 and H3-10
.
•
Use
U1-13 and U1-14 [Terminal A1, A2 Input Voltage]
to make sure that the analog input values
set to terminals A1 and A2 are applicable.
The motor characteristics and drive parameter settings are not compatible.
•
Set the correct V/f pattern to agree with the characteristics of the motor.
•
Examine the V/f pattern set in
E1-03 [V/f Pattern Selection]
.
•
Perform Rotational Auto-Tuning.
The drive is operating in vector control mode, but Auto-Tuning is not
completed.
•
Do Auto-Tuning.
•
Calculate motor data and reset motor parameters.
The Stall Prevention level during acceleration setting is too low.
Increase the value set in
L3-02 [Stall Prevent Level during Accel]
.
Note:
If the
L3-02
value is too low, the acceleration time can be unsatisfactorily long.
The Stall Prevention level during run setting is too low.
Increase the value set in
L3-06 [Stall Prevent Level during Run]
.
Note:
If the
L3-06
value is too low, speed will decrease while the drive outputs torque.
Drive reached the limitations of the V/f motor control method.
•
When the motor cable is longer than 50 m (164 ft), do Auto-Tuning for line-to-line resistance.
•
Set the V/f pattern to
“
High Starting Torque
”
.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...