10.5 Metasys N2 Communications
734
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
■
Metasys N2 Analog Input (AI) Summary
Table 10.15 Metasys N2 Analog Input Summary (Drive to Metasys N2)
Object ID
Object Name
Units
Drive Parameters
AI 1
Speed Reference
0.01 Hz
U1-01
AI 2
Output Speed
0.01 Hz
U1-02
AI 3
Output Current
0.1 A
UB-01
AI 4
kWatt Hour Meter
kWh
U4-10
AI 5
Output Power
0.1 kWh
U1-08
AI 6
Drive Temperature
1 °C
U4-08
AI 7
PI Feedback
0.01%
U5-01
AI 8
AC Output Voltage
0.1 Vac
U1-06
AI 9
DC Bus Voltage
1 Vdc
U1-07
AI 10
Fault Code
-
U2-01
AI 11
Elapsed Time - Hours
1 hour
U4-01
AI 12
Elapsed Time - 10K Hours
10K hours
U4-01
AI 13
MWatt Hour meter
MWh
U4-11
AI 14
Drive Rated Current
A
-
AI 15
Communication Error Code
-
U1-19
AI 16
PI Deviation
0.01%
U5-02
AI 17
PI Output Capacity
0.01%
U5-03
AI 18
PI Reference
0.01%
U5-04
AI 19
Last Fault Code
-
U2-02
AI 20
Freq Ref @ Fault
0.01 Hz
U2-03
AI 21
Output Freq @ Fault
0.01 Hz
U2-04
AI 22
Output Current @ Fault
0.1 A
U2-05
AI 23
Out Volt Ref @ Fault
0.1 Vac
U2-07
AI 24
DC Bus Volts @ Fault
1 Vdc
U2-08
AI 25
Output Power @ Fault
0.1 kW
U2-09
AI 26
Byp Input Terminal Status @ Fault
-
U2-11
AI 27
Byp Output Terminal Status @ Fault
-
U2-12
AI 28
Bypass Operation Status @ Fault
-
U2-13
AI 29
Elapsed Operation Time @ Fault
1 hour
U2-14
AI 30
Most Recent Fault
-
U3-01
AI 31
2nd Most Recent Fault
-
U3-02
AI 32
3rd Most Recent Fault
-
U3-03
AI 33
4th Most Recent Fault
-
U3-04
AI 34
Elapsed Time @ Current Fault
1 hour
U3-11
AI 35
Elapsed Time @ 2nd Fault
1 hour
U3-12
AI 36
Elapsed Time @ 3rd Fault
1 hour
U3-13
AI 37
Elapsed Time @ 4th Fault
1 hour
U3-14
AI 38
Read Parameter Data
-
-
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...