YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
303
■
2E: HAND Frequency Ref or Setpoint
Setting Value
Function
Description
2E
HAND Frequency Ref or
Setpoint
Enters the
S5-05 [HAND Frequency Reference]
value or the
S5-06 [HAND Setpoint]
value. When
S5-01 = 0 [HAND Frequency
Reference Source = HAND Analog Input]
and
S5-03 = 0 [HAND Mode PI Selection = Disabled]
, the drive enters HAND
Frequency Reference. When
b5-01 ≠ 0
,
S5-01 = 0
, and
S5-03 = 1 [Enabled]
, the drive enters HAND Setpoint.
◆
H4: Analog Outputs
H4 parameters
set the drive analog monitors. These parameters select monitor parameters, adjust gain and bias, and
select output signal levels.
■
Calibrate Meters Connected to MFAO Terminals FM and AM
To calibrate the meters connected to terminals FM and AM, use these parameters:
•
H4-02 [Terminal FM Analog Output Gain]
•
H4-03 [Terminal FM Analog Output Bias]
•
H4-05 [Terminal AM Analog Output Gain]
•
H4-06 [Terminal AM Analog Output Bias]
Set these parameters where the output voltage of 10 V and output current of 20 mA are 100% of the signal level. Use
jumper switch S5 and
H4-07 [Terminal FM Signal Level Select]
or
H4-08 [Terminal AM Signal Level Select]
to select
the voltage output and current output.
No.
Name
Range
Default
H4-02
Terminal FM Analog Output Gain
-999.9 - +999.9%
100.0%
H4-03
Terminal FM Analog Output Bias
-999.9 - +999.9%
0.0%
H4-05
Terminal AM Analog Output Gain
-999.9 - +999.9%
50.0%
H4-06
Terminal AM Analog Output Bias
-999.9 - +999.9%
0.0%
H4-07
Terminal FM Signal Level Select
0: 0 to 10 Vdc
2: 4 to 20 mA
0
H4-08
Terminal AM Signal Level Select
0: 0 to 10 Vdc
2: 4 to 20 mA
0
and
show the gain and bias when
H4-07 = 0 [0 to 10 Vdc]
and
H4-08 = 0 [0 to 10 Vdc]
.
Figure 5.63 Analog Output Gain/Bias Configuration Example 1
For example, when the parameter value set to analog output is 0, and a 3 V signal is output to terminal FM,
H4-03
[Terminal FM Analog Output Bias]
is set to 30%.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...