YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
601
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
b4-07
(0B34)
Expert
Terminal M5-M6 ON-
Delay Time
Sets the delay time to activate the contact after the function set in
H2-03
activates.
0 ms
(0 - 65000 ms)
b4-08
(0B35)
Expert
Terminal M5-M6 OFF-
Delay Time
Sets the delay time to deactivate the contact after the function set in
H2-03
deactivates.
0 ms
(0 - 65000 ms)
◆
b5: PID Control
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
b5-01
(01A5)
PID Mode Setting
Sets the type of PID control.
0 : Disabled
1 : Standard
3 : Fref + PID Trim
0
(0 - 3)
b5-02
(01A6)
RUN
Proportional Gain (P)
Sets the proportional gain (P) that is applied to PID input.
2.00
(0.00 - 25.00)
b5-03
(01A7)
RUN
Integral Time (I)
Sets the integral time (I) that is applied to PID input.
0.5 s
(0.0 - 360.0 s)
b5-04
(01A8)
RUN
Integral Limit
Sets the upper limit for integral control (I) as a percentage of the Maximum Output
Frequency.
100.0%
(0.0 - 100.0%)
b5-05
(01A9)
RUN
Derivative Time (D)
Sets the derivative time (D) for PID control. This parameter adjusts system responsiveness.
0.00 s
(0.00 - 10.00 s)
b5-06
(01AA)
RUN
PID Output Limit
Sets the maximum possible output from the PID controller as a percentage of the
Maximum Output Frequency.
100.0%
(0.0 - 100.0%)
b5-07
(01AB)
RUN
PID Offset Adjustment
Sets the offset for the PID control output as a percentage of the Maximum Output
Frequency.
0.0%
(-100.0 - +100.0%)
b5-08
(01AC)
RUN
Expert
PID Primary Delay Time
Constant
Sets the primary delay time constant for the PID control output. Usually it is not necessary
to change this setting.
0.00 s
(0.00 - 10.00 s)
b5-09
(01AD)
PID Output Level
Selection
Sets the polarity of the PID output.
0 : Normal Output (Direct Acting)
1 : Reverse Output (Reverse Acting)
0
(0, 1)
b5-10
(01AE)
RUN
PID Output Gain Setting
Sets the amount of gain to apply to the PID output.
1.00
(0.00 - 25.00)
b5-11
(01AF)
PID Output Reverse
Selection
Sets the function that enables and disables reverse motor rotation for negative PID control
output.
0 : Lower Limit is Zero
1 : Negative Output Accepted
0
(0, 1)
b5-17
(01B5)
RUN
PID Accel/Decel Time
Raises or lowers the PID setpoint using the acceleration and deceleration times set to the
drive. This is a soft-starter for the PID setpoint.
0.0 s
(0.0 - 6000.0 s)
b5-28
(01EA)
PID Feedback Square
Root Sel
Enables and disables the square root of the PID Feedback compared to the PID Setpoint to
set an appropriate drive output for the correct system regulation.
0 : Disabled
1 : Enabled
0
(0, 1)
b5-29
(01EB)
PID Feedback Square
Root Gain
Sets the multiplier applied to the square root of the feedback.
0.00
(0.00 - 2.00)
b5-30
(01EC)
PID Feedback Offset
Sets PID feedback Offset as a percentage of maximum frequency.
0.00%
(0.00 - 100.00%)
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...