SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
9.5
b: Application
◆
b1: Operation Mode Selection
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
b1-01
(0180)
Frequency Reference
Selection 1
Sets the input method for the frequency reference.
0 : Keypad
1 : Analog Input
2 : Serial Communications
3 : Option PCB
1
(0 - 3)
b1-02
(0181)
Run Command Selection
1
Sets the input method for the Run command.
0 : Keypad
1 : Digital Input
2 : Serial Communications
3 : Option PCB
7 : AUTO C Term Run
8 : AUTO C Serial Run
9 : AUTO C Option Run
7
(0 - 9)
b1-03
(0182)
Stopping Method
Selection
Sets the method to stop the motor after removing a Run command or entering a Stop
command.
0 : Ramp to Stop
1 : Coast to Stop
2 : DC Injection Braking to Stop
3 : Coast to Stop with Timer
1
(0 - 3)
b1-04
(0183)
Reverse Operation
Selection
Sets the reverse operation function. Disable reverse operation in fan or pump applications
where reverse rotation is dangerous.
0 : Reverse Enabled
1 : Reverse Disabled
1
(0, 1)
b1-08
(0187)
Run Command Select in
PRG Mode
Sets the conditions for the drive to accept a Run command entered from an external source
when using the keypad to set parameters.
0 : Disregard RUN while Programming
1 : Accept RUN while Programming
2 : Allow Programming Only at Stop
0
(0 - 2)
b1-11
(01DF)
Run Delay @ Stop
Sets the amount of time that the drive will not accept the Run command again after the
Run command is lost.
Note:
•
This parameter will operate for both AUTO Mode and HAND Mode.
•
This parameter will operate when the drive goes to sleep then wakes up.
•
The time set in this parameter does not apply for faults or Auto-Restarts.
•
When there is an active Run command while the time set in
b1-11
is active, the
keypad will show a
[Start Delay]
message as specified by the
o1-82 [Message Screen
Display]
display format.
0.0 s
(0.0 - 6000.0 s)
b1-12
(01E0)
Run Delay Memory
Selection
Sets how the drive saves the Run Delay Timer to the EEPROM during power loss.
0 : Disabled
1 : Only at Stop
2 : Running & Stop
2
(0 - 2)
b1-17
(01C6)
Run Command at Power
Up
Sets drive response when you apply power to drive that has an external Run command. Set
this parameter in applications where energizing or de-energizing the drive enables the Run
command.
0 : Disregard Existing RUN Command
1 : Accept Existing RUN Command
1
(0, 1)
b1-40
(3BCF)
Deceleration Abort Time
Sets the maximum time until the drive shuts off the output to decelerate to stop.
Note:
Set this parameter to 0.0 s to disable this function.
0.0 s
(0.0 - 6000.0 s)
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...