706
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Object ID
Object Name
(
Network Display, if
Different
)
Modbus Reg.
Precision
Range
Units
PV Access
AV18
DC Bus Voltage
0031h
XXXX.X
0-6553.5
V
R
AV19
PI Feedback Level
0038h
XXXX.X
0-100.0
%
R
AV20
PI Input Level
0039h
XXXX.X
0-100.0
%
R
AV21
PI Output Level
003Ah
XXXX.X
0-100.0
%
R
AV22
Drive SW Num
004Dh
XXXXX
0-65535
-
R
AV23
Bypass SW Num
8791h
XXXXX
0-65535
-
R
AV24
Comm Error Detail
003Dh
XXX
0-127
Bitmap
R
AV25
KVA Setting
0508h
XXXXX
-
Enumerated Data
Vendor Specific
R
AV26
Control Method
0043h
XXXXX
-
Enumerated Data
Vendor Specific
R
AV27
Accel Time
0200h
XXXX.X
0-6000.0
S
W
AV28
Decel Time
0201h
XXXX.X
0-6000.0
S
W
AV29
Parameter Number
####h
Determined in runtime
XXXXX
0-65535
-
W
AV30
Parameter Data
####h
Determined in runtime
XXXXX
0-65535
-
W
AV31
Motor Current
8780h
XXXX.X > 11 kVA
XXX.XX <= 11 kVA
0-6553.5 > 11 kVA
0-655.35 <= 11 kVA
A
R
AV32
120V to Kx Coils
8790h
XXXXX
0-65535
V
R
AV33
Drive kWh consumed
(
kWh consumed
)
005Ch -005Dh
XXXXXXXXX
0-999999999
kWh
R
AV34
Not Used AV34
-
-
-
-
R
AV35
Drive Run Time
004Ch
XXXXX
0-65535
Hours
R
AV36
Out Freq in %
003Fh
XXX.XX
0-100.00
%
R
AV37
Out Freq in RPM
003Eh
XXXXX
0-65535
RPM
R
AV38
Torque Iq (U6-01)
0051h
XXXX.X
0-6553.5
%
R
AV39
Drive HOA Status
004Bh
X
0-2
-
R
AV40
Last Drive Fault
Refer to page
for
information on fault
decimal values.
0081h
XXXXX
0-65535
-
R
AV41
Last Bypass Fault
Refer to page
for
information on fault
decimal values.
878Ch
XXXXX
0-65535
-
R
AV42
Current Sys Fault
(
Current Sys Flt
)
Refer to
for
information on fault
decimal values.
0080h
XXXXX
0-65535
-
R
■
Binary Input Objects
Object ID
Object Name
(
Network Display, if
Different
)
Modbus Reg.
Active Text
Inactive Text
PV Access
BI1
Drive Input Terminal 1
(
Input Terminal 1
)
002Bh:bit 0
ON
OFF
R
BI2
Drive Input Terminal 2
(
Input Terminal 2
)
002Bh:bit 1
ON
OFF
R
BI3
Drive Input Terminal 3
(
Input Terminal 3
)
002Bh:bit 2
ON
OFF
R
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...