452
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
28: Mirror HV600 M5-M6
Setting Value
Function
Description
28
Mirror HV600 M5-M6
The digital output activates when the HV600 drive digital output (M5-M6) is closed.
Use
H2-03 [Term H2-03
–
M5-M6 Function Selection]
to set the M5-M6 digital output. Refer to
for more information about setting values.
Note:
When the drive unit is OFF (in Bypass Mode in a 3-contactor configured bypass), this output will be OFF.
ON : Digital Output M5-M6 on HV600 is closed
OFF : Digital Output M5-M6 on HV600 is open
99: Not Used
Setting Value
Function
Description
99
Not Used
This setting allows serial communications to control the output.
■
Z2-30: Analog Input Signal Level Select
No.
(Hex.)
Name
Description
Default
(Range)
Z2-30
(8580)
Analog Input Signal Level
Select
Sets the input signal level for MFAI terminal A1.
0
(0 - 3)
0 : 0 to 10V (Lower Limit at 0)
2 : 4 to 20 mA
3 : 0 to 20 mA
■
Z2-32: Analog Input Gain Setting
No.
(Hex.)
Name
Description
Default
(Range)
Z2-32
(8582)
Analog Input Gain Setting
Sets the gain of the analog signal input to MFAI terminal A1.
100.0%
(-999.9 - +999.9%)
■
Z2-33: Analog Input Bias Setting
No.
(Hex.)
Name
Description
Default
(Range)
Z2-33
(8583)
Analog Input Bias Setting
Sets the bias of the analog signal input to MFAI terminal A1.
0.0%
(-999.9 - +999.9%)
◆
Z3: Bypass Control Serial Comm
■
Z3-12: Network Digital Inputs
No.
(Hex.)
Name
Description
Default
(Range)
Z3-12
(850B)
Network Digital Inputs
Enables and disables control of the digital inputs over a network. It is not necessary to wire to the
physical digital input.
0
(0, 1)
0 : Disabled
Serial communications physical digital inputs are ignored.
For MEMOBUS/Modbus (
H5-08 = 0
): Command Register 8402H is disabled.
For Metasys N2 (
H5-08 = 1
): Binary Outputs B05, B06, B07, B08, and B09 are disabled.
For P1 Apogee (
H5-08 = 2
): Points LDO44, LDO45, LDO46, LDO47, and LDO48 are disabled.
For BACnet (
H5-08 = 3
): BV72, BV73, BV74, BV75, BV76, BV77, BV78, and BV79 are disabled.
1 : Enabled
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...