222
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Refer to
for more information about available selections.
■
b5-70: System Unit Custom Character 3
No.
(Hex.)
Name
Description
Default
(Range)
b5-70
(3C21)
System Unit Custom
Character 3
Sets the third character of the custom unit display when
b5-46 = 49 [PID Unit Display Selection =
Custom (B5-68~70)]
.
41
(20 - 7A)
Refer to
for more information about available selections.
■
b5-71: Min PID Transducer Scaling
No.
(Hex.)
Name
Description
Default
(Range)
b5-71
(3C22)
Min PID Transducer Scaling
Sets the minimum PID level corresponding to the lowest analog input signal level.
0.00
(-99.99 - +99.99)
Note:
•
To enable this parameter, you must set
b5-71
<
b5-38 [PID User Unit Display Scaling]
. If you set
b5-71
>
b5-38
, the drive will disable all
PID analog inputs.
•
Parameters
b5-46 [PID Unit Display Selection]
,
b5-38
, and
b5-39 [PID User Unit Display Digits]
set the unit, range, and resolution.
When you set
b5-71 < 0
, the drive appropriately scales the setpoint and feedback values of the drive, but internally
limits to 0 when the reported value from the transducer is negative.
shows an example of the transducer scaling lower limit when:
•
b5-01 = 1 [PID Mode Setting = Standard]
•
b5-46 = 3 [°F: Fahrenheit]
•
b5-71 < 0.00
•
H3-09 = 0 [Terminal A2 Signal Level Select = 0-10V (LowLim=0)]
•
H3-10 = B [Terminal A2 Function Selection = PID Feedback]
b5-38: PID User Unit Display Scaling
b5-71: Min PID Transducer Scaling
U5-01: PID Feedback
Figure 5.26 Transducer Scaling Lower Limit
■
b5-82: Feedback Loss 4
~
20mA Detect Sel
No.
(Hex.)
Name
Description
Default
(Range)
b5-82
(31B0)
Feedback Loss 4
~
20mA
Detect Sel
Sets the drive to do a 4 to 20 mA wire-break detection on the analog input set for PID feedback.
2
(0 - 3)
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...