210
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Note:
If you set more than one of
H3-02 and H3-10
to
16
, the drive will detect
oPE07 [Analog Input Selection Error]
.
■
PID Control Block Diagram
Figure 5.23 PID Block Diagram
*1
The drive uses the largest value of
Y1-06 [Minimum Speed]
,
Y4-12 [Thrust Frequency]
, or
d2-02 [Frequency Reference Lower Limit]
for
Lower I Limit. When the drive is in Emergency Override Mode, it uses the largest value of
Y1-06
,
Y4-12
,
d2-02
, or
S6-09 [Emergency
Override Min Speed]
.
*2
The drive uses the smallest value of
Y1-40 [Maximum Speed]
,
E1-04 [Maximum Output Frequency]
, or
d2-01 [Frequency Reference
Upper Limit]
for Upper I Limit. When the drive is in Emergency Override Mode, it uses the smallest value of
Y1-40
,
E1-04
,
d2-01
, or
S6-
10 [Emergency Override Max Speed]
.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...