5.10 o: Keypad-Related Settings
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
357
10 :
°
C: Celsius
11 : m: meters
12 : ft: feet
13 : L/min: liters/min
14 : m
3
/min: cubic meters/min
15 : “Hg: Inch Mercury
16 : kPa: kilopascal
48 : %: Percent
49 : Custom(o1-13~15)
50 : None
■
o1-10: User Units Maximum Value
No.
(Hex.)
Name
Description
Default
(Range)
o1-10
(0520)
User Units Maximum Value
Sets the value that the drive shows as the maximum output frequency.
Determined by o1-03
(1 - 60000)
To display a maximum output frequency of 100.00, set parameters to these values:
•
o1-10 = 10000
•
o1-11 = 2 [User Units Decimal Position = 2 Dec (XXX.XX)]
Note:
Set
o1-03 = 3 [Frequency Display Unit Selection = User Units (o1-10 & o1-11)]
before you set
o1-10
and
o1-11
.
■
o1-11: User Units Decimal Position
No.
(Hex.)
Name
Description
Default
(Range)
o1-11
(0521)
User Units Decimal Position
Sets the number of decimal places for frequency reference and monitor values.
Determined by o1-03
(0 - 3)
0 : No Decimal Places (XXXXX)
1 : One Decimal Places (XXXX.X)
2 : Two Decimal Places (XXX.XX)
3 : Three Decimal Places (XX.XXX)
Note:
Set
o1-03 = 3 [Frequency Display Unit Selection = User Units (o1-10 & o1-11)]
before you set
o1-10 [User Units Maximum Value]
and
o1-
11
.
■
o1-13: Freq. Reference Custom Unit 1
No.
(Hex.)
Name
Description
Default
(Range)
o1-13
(3105)
Freq. Reference Custom
Unit 1
Sets the first character of the custom unit display when
o1-03 = 3 [Frequency Display Unit Selection
= User Units]
and
o1-09 = 49 [Freq. Reference Display Units = Custom (o1-13~15)]
.
41
(20 - 7A)
Refer to
for more information about available selections.
■
o1-14: Freq. Reference Custom Unit 2
No.
(Hex.)
Name
Description
Default
(Range)
o1-14
(3106)
Freq. Reference Custom
Unit 2
Sets the second character of the custom unit display when
o1-03 = 3 [Frequency Display Unit
Selection = User Units]
and
o1-09 = 49 [Freq. Reference Display Units = Custom (o1-13~15)]
.
41
(20 - 7A)
Refer to
for more information about available selections.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...