SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
215
■
b5-01: PID Mode Setting
No.
(Hex.)
Name
Description
Default
(Range)
b5-01
(01A5)
PID Mode Setting
Sets the type of PID control.
0
(0 - 3)
0 : Disabled
1 : Standard
The drive does D control on the difference between the feedback value and the PID setpoint output through
U5-02
[PID Input]
.
3 : Fref + PID Trim
The drive adds the frequency reference to the PID output. The drive does D control on the difference between the
feedback value and the PID setpoint output through
U5-02
.
Note:
•
When you set
b5-01 = 1 or 3
from the keypad, the drive will automatically set
H3-10 = B [Terminal A2 Function Selection = PID
Feedback]
and
o1-26 = 501 [Custom Monitor 3 = PID Feedback]
. The drive will also update the defaults for
H3-10
and
o1-26
when you
change
b5-01
.
•
When you set
b5-01 = 0
from the keypad, the drive will automatically set
H3-10 = 0 [Frequency Reference]
and
o1-26 = 103 [Output
Current]
.
•
When you set
b5-01
from a different method, for example MEMOBUS, the drive will automatically update the defaults for
H3-10
and
o1-
26
, but it will not update the parameters.
■
b5-02: Proportional Gain (P)
No.
(Hex.)
Name
Description
Default
(Range)
b5-02
(01A6)
RUN
Proportional Gain (P)
Sets the proportional gain (P) that is applied to PID input.
2.00
(0.00 - 25.00)
Larger values decrease errors, but can cause oscillations. Smaller values let too much offset between the setpoint and
feedback.
Set
b5-02 = 0.00
to disable P control.
■
b5-03: Integral Time (I)
No.
(Hex.)
Name
Description
Default
(Range)
b5-03
(01A7)
RUN
Integral Time (I)
Sets the integral time (I) that is applied to PID input.
0.5 s
(0.0 - 360.0 s)
Set a short integral time in
b5-03
to remove the offset faster. If the integral time is too short, it can cause overshoot or
oscillation.
Set
b5-03 = 0.0
to disable I control.
Figure 5.25 Integral Time and Deviation
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...