672
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
9.18
U: Monitors
◆
U1: Operation Status Monitors
No.
(Hex.)
Name
Description
MFAO Signal Level
U1-01
(0040)
Frequency Reference (AI)
Shows the frequency reference value. Parameter
o1-03 [Keypad Display Unit Selection]
sets the
display units.
Unit: 0.01 Hz
10 V = Maximum frequency
(0 V to +10 V)
U1-02
(0041)
Output Frequency
Shows the output frequency. Parameter
o1-03 [Keypad Display Unit Selection]
sets the display units.
Unit: 0.01 Hz
10 V = Maximum frequency
(0 V to +10 V)
U1-03
(0042)
Output Current
Shows the output current.
The keypad shows the value of
U1-03
in amperes (A). When you use serial communications to show
the monitor, the current is
“
8192 = drive rated current (A)
”
. Use the formula:
“
Numerals being
displayed / 8192 × drive rated current (A)
”
to use the serial communication current value shown in
the monitor.
Unit: Determined by the drive model.
•
0.01 A: 2011 to 2046, 4005 to 4014
•
0.1 A: 2059 to 2273, 4021 to 4302
10 V = Drive rated current
U1-04
(0043)
Control Method
Shows the drive control method.
0 : V/f Control
No signal output available
U1-06
(0045)
Output Voltage Ref
Shows the output voltage reference.
Unit: 0.1 V
208/240 V: 10 V = 200 Vrms
480 V: 10 V = 400 Vrms
U1-07
(0046)
DC Bus Voltage
Shows the DC bus voltage.
Unit: 1 V
208/240 V: 10 V = 400 V
480 V: 10 V = 800 V
U1-08
(0047)
Output Power
Shows the internally-calculated output power.
Unit: Determined by the drive model.
•
0.01 kW: 2011 to 2046, 4005 to 4014
•
0.1 kW: 2059 to 2273, 4021 to 4302
10 V: Drive capacity (motor
rated power) kW
(-10 V to +10 V)
U1-10
(0049)
Input Terminal Status
Shows the status of the MFDI terminal where 1 = (ON) and 0 = (OFF).
For example,
U1-10
shows
“
00000011
”
when terminals S1 and S2 are ON.
bit0 : Terminal S1 (MFDI 1)
bit1 : Terminal S2 (MFDI 2)
bit2 : Terminal S3 (MFDI 3)
bit3 : Terminal S4 (MFDI 4)
bit4 : Terminal S5 (MFDI 5)
bit5 : Terminal S6 (MFDI 6)
bit6 : Terminal S7 (MFDI 7)
bit7 : Not used (normal value of 0).
No signal output available
U1-11
(004A)
Output Terminal Status
Shows the status of the MFDO terminal where 1 = (ON) and 0 = (OFF).
For example,
U1-11
shows
“
00000011
”
when terminals M1 and M3 are ON.
Note:
When
H2-xx = 100 to 1C4 [Inverse Output of Function]
, the monitor will show the value before
inversion.
bit 0 : Terminals M1-M2
bit 1 : Terminals M3-M4
bit 2 : Terminals M5-M6
bit 3 : Not used (normal value of 0).
bit 4 : Not used (normal value of 0).
bit 5 : Not used (normal value of 0).
bit 6 : Not used (normal value of 0).
bit 7 : Fault relay MA/MB-MC
No signal output available
U1-12
(004B)
Drive Status
Shows drive status where 1 = ON and 0 = OFF.
For example,
U1-12
shows
“
00000101
”
during run with the Reverse Run command.
bit0 : During Run
bit1 : During zero-speed
bit2 : During reverse
bit3 : During fault reset signal input
bit4 : During speed agreement
bit5 : Drive ready
bit6 : During minor fault detection
bit7 : During fault detection
No signal output available
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...